Figure 2: Possible characteristic measuring value curves

5.1.3.1 Example of Numerical Teaching:

1) The measuring range is to be set between 150mm (A) and 300mm (B) (characteristic curve 2).

Point A, absolute value in 0.1 mm:

1500

05DC hex (= Measuring range limit A)

Point B, absolute value in 0.1 mm:

3000

0BB8 hex (= Measuring range limit B)


Parameter to be written:
Measuring range work:

05DC0BB8 hex

Save parameters to permanently store the values!


2) An inverted measuring range is to be set between 200mm (B) and 400mm (A) (characteristic curve 3).

Point A, absolute value in 0.1 mm:

4000

0FA0 hex (= Measuring range limit A)

Point B, absolute value in 0.1 mm:

2000

07D0 hex (= Measuring range limit B)


Parameter to be written:
Measuring range work:

0FA007D0 hex

Save parameters to permanently store the values!