Connection object, class 0x05, Class attributes – Baumer GK473 User Manual

Page 13

Advertising
background image

Manual_GK473_DeviceNet_EN.doc

13/31

Baumer IVO GmbH & Co. KG

04.05.11

Villingen-Schwenningen,

Germany

Connection Object, Class 0x05

Class Attributes

Attribute ID

Access Rule

Name

DeviceNet

Data type

Value

1 Get Revision

UINT 0x0001

Class Services

Service Code

Get Attribute Single

0x0E

Create 0x08



Instance 1 = Explicit Messaging Connection
Instance 2 = I/O Poll Connection
Instance 4 = Change of State (COS) Connection

Instance 2

IO Poll Connection Attributes

Attribute

ID

Access

Rule

Name

DeviceNet

Data type

Value

Description

1 Get

State

USINT

0x01

0 = Non existent
1 = Configuring
3 = Established
4 = Timeout

2

Get

Instance type

USINT

0x01

I/O Connection

3

Get

Transport Class Trigger

BYTE

0x83

Defines the behaviour of the connection

4

Get

Produced Connection ID

UINT

0x3FF

CAN ID for transmission

5

Get

Consumed Connection ID UINT

0x5FD

CAN ID for reception

6 Get

Initial Comm
Characteristics

BYTE

0x01

Defines Message Groups to
consume/produce date

7

Get

Produced Connection Size

UINT

0x0030

Number of bytes transmitted across
this connection

8 Get

Consumed Connection
Size

UINT

0x0000

Number of bytes received across
this connection

9

Get/Set Expected Packet Rate

UINT

Timing associated with this connection

12

Get

Watchdog Time out action

USINT

0x00

0 = Transition to the timed out state
1 = Auto Delete
2 = Auto Reset
3 = Deferred Delete

13 Get

Produced Connection Path
length

UINT

0x0006

Number of bytes in the produced
Connection path attribute

14

Get

Produced Connection Path

EPATH

0x200424653003

Application object producing data
on this connection

15 Get

Consumed connection
Path length

UINT

0x0006

Number of bytes in the consumed
Connection path length attribute

16 Get

Consumed Connection
Path

EPATH

0x200424653003

Specifies the application object(s)
that are to receive the data consumed
by this connection object

17

Get/Set Production Inhibit Time

UINT

0x0000

Production Inhibit Time

Instance Services

Service Code

Delete 0x09
Reset 0x05
Apply Attributes

0x0D

Get Attribute Single

0x0E

Set Attribute Single

0x10

Advertising