6.7. Alarms

Diagnosis alarms are triggered in line with acyclic services according to DPV1.
A diagnosis alarm is triggered upon the encoder having detected a probably incorrect position. The next
position data telegram is added a high priority bit in the function code (bit 1) by the encoder what makes the
control transmit a acyclic diagnosis alarm request. The encoder responds by an acyclic diagnosis telegram.
“Data Unit” (DU) of this telegram provides the following structure: Octets 1 to 6 correspond to the diagnosis
telegram of cyclic data exchange.

Data Unit:

Value Significance

Octet 1

Station_status_1

Diverse bits, see PROFIBUS literature (e.g. Ext. Diagnose
Bit)

Octet 2

Station_status_2

Diverse bits, see PROFIBUS literature (e.g. Stat. Diagnose
Bit)

Octet 3

Station_status_3

External diagnosis overflow bit

Octet 4

Diag_Master_Add

Master address after parameterization (otherwise 0xFF)

Octet 5

Ident_Number

Ident number high byte

Octet 6

Ident_Number

Ident number low byte

Octet 7

Block Length

0x07

Following block length in bytes (including this one)

Octet 8

Alarmtyp

0x01

1 = Diagnostic alarm

Octet 9

Slot

0x01

Slot number

Octet 10

Alarm Spec

xx

Alarm Specifier (in / out) and sequence number (0..31)

Octet 11

Header

0x81

see DPV2 encoder profile

Octet 12

Channel

0x40

see DPV2 encoder profile

Octet 13

Type of Diagnosis 0x16

see DPV2 encoder profile / Alarm definition



The alarm is acknowledged by the control under reference to the running alarm sequence number.

The encoder will only consider value 22 (0x16) indicating a position error as „Type of Diagnosis / Alarm
Definition).

A diagnosis alarm is triggered once with each inbound and outbound event. An outbound event alarm
comprises an „Alarm Specifier“ for „outbound event“ together with a specific sequence number that is
incremented towards the inbound event.

Siemens controls proceed diagnosis OB82 in case of alarm. If this is not implemented in the project the
control will go to STOP in case of alarm.

Alarms resulting from a probably incorrect position can be signalized in three different ways:

DPV1 Diagnosis alarm (as described)

E

rror signal in G1_XIST2 (see under „Error signals in G1_XIST2“)

LED in the bus cover is red continuous for at least 2.5 s