Manual_ProfibusDPV2_BIDE_EN.docx

27/41

Baumer IVO GmbH & Co. KG

22.11.12

Villingen-Schwenningen, Germany

6.9.8. PROFIdrive parameter 971 transfer to non-volatile memory
By calling this parameter all volatile parameter are stored into the encoder’s non-volatile memory. At the
present DPV2 encoder this procedure relates only to the preset value (profile parameter 65000). The saving
operation is performed in DS_WRITE.

DS_WRITE

DP-V1 Header

Called parameter Value

Example

Function ID

Permanent for DS_Write

0x5F

ID

Slot no.1 (E/A address telegram81)

0x0200

Index

47 = 0x2F

0x2F

Length

10 = 0x0A

0x0A

Data Unit - (write):

Byte #

Example

0

Request Reference (example)

0xAA

1

Request ID=0x01 Change ID=0x02

0x01

2

Shaft no. (0=whole device)

0x00

3

Number of parameters

0x01

4

Attribute = “Value”

0x10

5

Number of parameter elements

0x01

6

Prm_no hi: 971 = 0x03CB

0x03

7

Prm_no lo: 971 = 0x03CB

0xCB

8

Subindex hi

0x00

9

Subindex lo

0x00

10

Format Word

0x06

11

Number of values

0x01

12

Save command (MSB)

0x00

13

Save command (LSB)

0x01


DS_READ

DP-V1 Header

Called parameter Value

Function ID

Permanent for DS_Read

0x5E

ID

Slot no.1 (E/A address telegram81)

0x0200

Index

47 = 0x2F

0x2F

Max.Length

64 = 0x40

0x40

Data Unit - (read):

Byte #

Example

0

Request Reference: mirrored

0xAA

1

Request ID (not: Change)

0x01

2

Shaft no. (0=whole device)

0x00

3

Number of parameters

0x01

4

Format: Unsigned16

0x06

5

Number of values

0x01

6

Value (hi): ever 0

0x00

7

Value (lo): ever 0

0x00