Table 3 — Fan Rpm at Motor Pulley Settings*
UNIT
48TJ
MOTOR PULLEY TURNS OPEN
0
1
⁄
2
1
1
1
⁄
2
2
2
1
⁄
2
3
3
1
⁄
2
4
4
1
⁄
2
5
5
1
⁄
2
6
008†
840
815
790
765
740
715
690
665
640
615
590
—
—
008**
935
910
885
860
835
810
785
760
735
710
685
—
—
009†
935
910
885
860
835
810
785
760
735
710
685
—
—
012†
935
910
885
860
835
810
785
760
735
710
685
—
—
012††
1085
1060
1035
1010
985
960
935
910
885
860
835
—
—
014†
1080
1060
1035
1015
990
970
950
925
905
880
860
—
—
014††
1260
1220
1185
1155
1130
1100
1075
1045
1015
990
960
930
900
*Approximate rpm shown.
†Indicates standard motor and drive.
**Indicates alternate drive.
††Indicates alternate motor and drive.
MOTOR MOUNTING
PLATE NUTS
Fig. 34 — Typical Belt-Drive Motor Mounting
for Sizes 008,009
Fig. 35 — Typical Belt-Drive Motor Mounting
for Sizes 012,014
Fig. 36 — Evaporator-Fan Pulley Adjustment