Route thermostat cable or equivalent single leads of col-

ored wire from subbase terminals to low-voltage connec-
tions on unit (shown in Fig. 11) as described in Steps 1 - 4
below.
1. If unit is mounted on roof curb and accessory thru-the-

curb service plate connection is used, route wire through
connection plate.

2. Pass control wires through the hole provided on unit

(see connection D in Connection Sizes table in Fig. 7).

3. Feed wires through the raceway built into the corner post

to the 24-v barrier located on the left side of the control

box. See Fig. 12. The raceway provides the UL-required
(Underwriters’ Laboratories) clearance between high- and
low-voltage wiring.

4. Connect thermostat wires to screw terminals on low-

voltage connection board.

HEAT ANTICIPATOR SETTINGS — Set heat anticipator
settings at .14 amp for the first stage and .20 amp for second-
stage heating.

Table 2 — Electrical Data

UNIT
48TJ

NOMINAL
VOLTAGE

(60 Hz)

IFM

TYPE

VOLTAGE

RANGE

COMPR

(ea)

OFM

(ea)

IFM

COMBUSTION

FAN MOTOR

POWER SUPPLY

DISCONNECT

SIZE*

Min

Max

RLA

LRA

Hp

FLA

FLA

FLA

MCA

MOCP†

FLA

LRA

008

(7

1

2

Tons)

208/230

(3 phase)

Std

187

254

13.6

73.4

1

4

1.4

5.8

.57

39.2/39.2

45/45

41/41

194/194

460

(3 phase)

Std

414

508

6.2

37.7

1

4

0.8

2.6

.30

18.0

25

19

99

575

(3 phase)

Std

518

632

4.9

31.0

1

4

0.8

2.6

.30

14.2

20

15

81

009

(8

1

2

Tons)

208/230

(3 phase)

Std

187

254

15.8

92.0

1

4

1.4

5.8

.57

44.2/44.2

50/50

46/46

231/231

460

(3 phase)

Std

414

508

7.4

46.0

1

4

0.8

2.6

.30

20.7

25

22

116

575

(3 phase)

Std

518

632

5.9

44.0

1

4

0.8

2.6

.30

16.5

20

17

107

012

(10 Tons)

208/230

(3 phase)

Std

187

254

17.9

110.0

1

4

1.4

5.8

.57

48.9/48.9

60/60

51/51

267/267

Alt

7.5

50.6/50.6

60/60

53/53

286/286

460

(3 phase)

Std

414

508

8.6

55.0

1

4

0.8

2.6

.30

23.4

30

24

134

Alt

3.4

24.2

30

25

173

575

(3 phase)

Std

518

632

6.4

44.0

1

4

0.8

2.6

.30

17.6

20

18

107

Alt

3.4

18.2

20

19

139

014

(12

1

2

Tons)

208/230

(3 phase)

Std

187

254

23.0

146.0

1

4

1.4

10.6

.57

65.2/65.2

80/80

68/68

383/383

Alt

15.0

69.6/69.6

80/80

73/73

406/406

460

(3 phase)

Std

414

508

10.4

73.0

1

4

0.8

4.8

.30

29.6

35

31

192

Alt

7.4

32.2

35

34

203

575

(3 phase)

Std

518

632

8.3

58.4

1

4

0.8

4.8

.30

23.6

30

25

154

Alt

7.4

25.7

35

27

163

LEGEND

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

UL

Underwriters’ Laboratories

*Used to determine minimum disconnect size per NEC.

†Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent voltage imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

NOTE: The 575-v 48TJ008-014 units are UL, Canada, only.

Determine maximum deviation from average voltage.

(AB) 457 - 452 = 5 v
(BC) 464 - 457 = 7 v
(AC) 457 - 455 = 2 v

Maximum deviation is 7 v.

Determine percent voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

9