Table 7 — Fan Performance, 48TJ008 — Vertical Discharge Units

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

2200

506

0.52

586

0.72

656

0.95

718

1.18

776

1.43

838

1.78

898

2.21

935

2.58

2250

514

0.55

593

0.76

662

0.99

724

1.22

781

1.78

841

1.81

902

2.25

939

2.60

2300

521

0.57

600

0.79

668

1.02

730

1.26

786

1.50

843

1.83

905

2.28

943

2.62

2400

536

0.63

613

0.85

680

1.09

741

1.34

796

1.59

849

1.88

910

2.31

952

2.74

2500

551

0.69

626

0.93

693

1.17

753

1.43

808

1.69

859

1.96

912

2.31

963

2.81

2550

559

0.72

634

0.97

700

1.21

759

1.48

814

1.74

864

2.01

915

2.34

968

2.81

2600

567

0.75

641

1.00

706

1.25

764

1.52

819

1.79

869

2.06

918

2.37

973

2.81

2700

582

0.83

655

1.08

719

1.34

776

1.61

831

1.89

880

2.17

927

2.47

976

2.84

2800

598

0.90

670

1.17

732

1.43

789

1.71

842

2.00

892

2.29

938

2.58

983

2.92

2900

614

0.98

684

1.25

745

1.53

802

1.81

854

2.11

903

2.42

949

2.71

993

3.03

3000

630

1.07

699

1.35

759

1.63

815

1.92

866

2.23

915

2.54

961

2.85

1003

3.17

3100

646

1.16

714

1.45

773

1.74

828

2.04

878

2.35

926

2.67

972

3.00

1015

3.32

3200

662

1.26

729

1.55

787

1.86

841

2.16

891

2.48

938

2.81

983

3.14

1026

3.47

3300

679

1.36

744

1.66

801

1.98

854

2.29

904

2.61

950

2.95

995

3.30

3400

695

1.47

759

1.78

816

2.10

867

2.42

917

2.75

963

3.10

1007

3.45

3500

712

1.59

774

1.90

830

2.23

881

2.56

930

2.90

976

3.25

3600

729

1.71

790

2.03

845

2.37

895

2.71

943

3.05

988

3.41

3700

745

1.84

805

2.17

860

2.52

909

2.87

956

3.22

3750

754

1.91

813

2.24

868

2.59

917

2.95

963

3.30

LEGEND

Bhp — Brake Horsepower Input to Fan
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 4.)

2.

indicates alternate drive required.

3.

indicates field-supplied motor and drive required.

4. Standard drive range is 590 to 840 rpm. Alternate drive range is

685 to 935 rpm. All other rpms require a field-supplied drive.

5. Values include losses for filters, unit casing, and wet coils.
6. Maximum continuous bhp is 2.4. Extensive motor and electrical

testing on these units ensures that the full range of the motor can
be utilized with confidence. Using your fan motors up to the rat-
ings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected.

7. Use of a field-supplied motor may affect wire sizing. Contact your

Carrier representative to verify.

8. Interpolation is permissible. Do not extrapolate.

Table 8 — Fan Performance, 48TJ009 — Vertical Discharge Units

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

2550

559

0.72

634

0.97

700

1.21

759

1.48

814

1.74

864

2.01

915

2.34

968

2.81

2600

567

0.75

641

1.00

706

1.25

764

1.52

819

1.79

869

2.06

918

2.37

973

2.81

2700

582

0.83

655

1.08

719

1.34

776

1.61

831

1.89

880

2.17

927

2.47

976

2.84

2800

598

0.90

670

1.17

732

1.43

789

1.71

842

2.00

892

2.29

938

2.58

983

2.92

2900

614

0.98

684

1.25

745

1.53

802

1.81

854

2.11

903

2.42

949

2.71

993

3.03

3000

630

1.07

690

1.35

759

1.63

815

1.92

866

2.23

915

2.54

961

2.85

1003

3.17

3100

646

1.16

714

1.45

773

1.74

828

2.04

878

2.35

926

2.67

972

3.00

1016

3.32

3200

662

1.26

729

1.55

787

1.86

841

2.16

891

2.48

938

2.81

983

3.14

1026

3.47

3300

679

1.36

744

1.66

801

1.98

854

2.29

904

2.61

950

2.95

995

3.30

3400

695

1.47

759

1.78

816

2.10

867

2.42

917

2.75

963

3.10

1007

3.45

3500

712

1.59

774

1.90

830

2.23

881

2.56

930

2.90

976

3.25

3600

729

1.71

790

2.03

845

2.37

895

2.71

943

3.05

988

3.41

3700

745

1.84

805

2.17

860

2.52

909

2.87

956

3.22

3750

754

1.91

813

2.24

868

2.59

917

2.95

963

3.30

3800

762

1.98

821

2.31

875

2.66

924

3.03

970

3.38

3900

779

2.12

836

2.46

890

2.82

938

3.19

4000

796

2.27

852

2.61

905

2.98

953

3.37

4100

813

2.42

868

2.78

920

3.15

4200

830

2.59

884

2.95

935

3.33

4250

839

2.68

890

3.04

4300

847

2.76

900

3.13

LEGEND

Bhp — Brake Horsepower Input to Fan
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)

2.

indicates field-supplied motor and drive required.

3. Standard drive range is 685 to 935 rpm. All other rpms require a

field-supplied drive.

4. Values include losses for filters, unit casing, and wet coils.

5. Maximum continuous bhp is 2.4. Extensive motor and electrical

testing on these units ensures that the full range of the motor can
be utilized with confidence. Using your fan motors up to the rat-
ings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected.

6. Use of a field-supplied motor may affect wire sizing. Contact your

Carrier representative to verify.

7. Interpolation is permissible. Do not extrapolate.