Fig. 7 — base unit dimensions – Carrier 48TJD008-014 User Manual

Page 7

Advertising
background image

UNIT
48TJ

STANDARD

UNIT

WEIGHT

CORNER

WEIGHT

(A)

CORNER

WEIGHT

(B)

CORNER

WEIGHT

(C)

CORNER

WEIGHT

(D)

‘‘H’’

‘‘J’’

‘‘K’’

‘‘L’’

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

ft-in.

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

D/E/F008

870

395

189

86

161

73

239

109

280

127 1-2

7

8

378 3-5

5

16

1050 2-9

11

16

856 2- 2

7

16

672

D/E/F009

880

399

191

87

163

74

242

110

284

129 3-3

7

8

1013 3-5

5

16

1050 2-9

11

16

856 2- 2

7

16

672

D/E/F012

1035

469

225

102

192

87

285

129

333

151 2-5

7

8

759 4-1

5

16

1253 3-0

3

8

924 2-10

7

16

875

D/E014

1050

476

228

103

195

88

289

131

338

153 1-2

7

8

378 4-1

5

16

1253 3-0

3

8

924 2-10

7

16

875

NOTES:
1. Dimensions in [

] are in millimeters.

2.

Center of gravity.

3.

Direction of airflow.

4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For

horizontal discharge units field-supplied flanges should be attached to horizontal dis-
charge openings, and all ductwork should be attached to the flanges.

5. Minimum clearance (local codes or jurisdiction may prevail):

a. Between unit (flue side) and combustible surfaces, 48 inches.

b. Bottom of unit to combustible surfaces (when not using curb) 1 inch.

Bottom of base rail to combustible surfaces (when not using curb) 0 inches.

c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side get-

ting the greater clearance is optional.

d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC (National Electrical Code).
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces, control

box side, 42 in. per NEC.

h. Horizontal supply and return end, 0 inches.

6. With the exception of the clearance for the condenser coil and combustion side as

stated in Notes 5a, b, and c, a removable fence or barricade requires no clearance.

7. Units may be installed on combustible floors made from wood or Class A, B, or C

roof covering material if set on base rail.

8. The vertical center of gravity is 1

Ј

-7

Љ

[483] up from the bottom of the base rail. Hori-

zontal center of gravity is shown.

CONNECTION SIZES

A

1

3

8

Љ

Dia [35] Field Power Supply Hole

B

2-

1

2

Љ

Dia [64] Power Supply Knock-Out

C

1

3

4

Љ

Dia [44] Charging Port Hole

D

7

8

Љ

Dia [22] Field Control Wiring Hole

E

3

4

Љ

—14 NPT Condensate Drain

F

1

2

Љ

—14 NPT Gas Connection 48TJD008 & 009

3

4

Љ

—14 NPT Gas Connection 48TJE/F008 & 009;

48TJD/E012,014, 48TJF012

G

2

Љ

Dia [51] Power Supply Knock-Out

Fig. 7 — Base Unit Dimensions

BOTTOM POWER CHART, THESE HOLES

REQUIRED FOR USE WITH ACCESSORY

PACKAGES — CRBTMPWR001A00,

OR CRBTMPWR002A00

THREADED

CONDUIT SIZE

WIRE SIZE

REQUIRED HOLE

SIZES (MAX)

1

2

؆

24 V

7

8

Љ

[22.2]

3

4

؆

Power*

1

1

8

Љ

[28.4]

1

1

4

؆

Power*

1

3

4

Љ

[44.4]

*Select either

3

4

Љ

or 1

1

4

Љ

for power, depending on wire size.

7

Advertising