Carrier 48TJD008-014 User Manual

Page 35

Advertising
background image

Table 21 — Heating Service Troubleshooting

PROBLEM

CAUSE

REMEDY

Burners will not
ignite.

Misaligned spark electrodes.

Check flame ignition and sensor electrode positioning.
Adjust as needed.

No gas at main burners.

Check gas line for air purge as necessary. After purging
gas line of air, allow gas to dissipate for at least 5 min-
utes before attempting to relight unit.
Check gas valve.

Water in gas line.

Drain water and install drip leg to trap water.

No power to furnace.

Check power supply, fuses, wiring, and circuit breaker.

No 24 v power supply to control circuit.

Check transformer. Transformers with internal overcur-
rent protection require a cool down period before
resetting.

Miswired or loose connections

Check all wiring and wirenut connections.

Burned-out heat anticipator in thermostat.

Replace thermostat.

Broken thermostat wires.

Run continuity check. Replace wires, if necessary.

Inadequate heating.

Dirty air filter.

Clean or replace filter as necessary.

Gas input to unit too low.

Check gas pressure at manifold. Clock gas meter for
input. If too low, increase manifold pressure, or replace
with correct orifices.

Unit undersized for application.

Replace with proper unit or add additional unit.

Restricted airflow.

Clean filter, replace filter, or remove any restrictions.

Blower speed too low.

Use high speed tap, increase fan speed, or install op-
tional blower, as suitable for individual units.

Limit switch cycles main burners.

Check rotation of blower, thermostat heat anticipator set-
tings, and temperature rise of unit. Adjust as needed.

Too much outdoor air.

Adjust minimum position.
Check economizer operation.

Poor flame
characteristics.

Incomplete combustion (lack of combustion air)
results in:
Aldehyde odors, CO, sooting flame, or floating flame.

Check all screws around flue outlets and burner com-
partment. Tighten as necessary.
Cracked heat exchanger.
Overfired unit — reduce input, change orifices, or adjust
gas line or manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.

Burners will not
turn off.

Unit is locked into Heating mode for a one minute
minimum.

Wait until mandatory one minute time period has
elapsed or power to unit.

LEGEND AND NOTES FOR FIG. 48

IMPORTANT:

Refer

to

unit

wiring

label

for

actual

unit

wiring information.

NOTES:
1. If any of the original wire furnished must be replaced, it must be

replaced with type 90 C wire or its equivalent.

2. Three-phase motors are protected under primary single phasing

conditions.

3. Thermostat: HH07AT170, 172, 174 and P272-2783

Subbase: HH93AZ176, 178 and P272-1882, 1883

4. Set heat anticipator for first stage at 0.14 amp, second stage at

0.2 amp.

5. Use copper conductors only.
6. TRAN is wired for 230 v unit. If unit is to be run with 208 v power

supply, disconnect BLK wire from 230 v tap (RED) and connect to
200 v tap (BLU). Insulate end of 230 v tap.

7. When economizer assembly is installed move GRA wire from con-

nection board (Y1) to GRA wire from PL6,5; move ORN wire from
connection board (Y2) to ORN wire from PL6,9, on economizer
assembly.

AHA

Adjustable Heat Anticipator

BR

Burner Relay

C

Contactor, Compressor

CAP

Capacitor

CB

Circuit Breaker

CC

Cooling Compensator

COMP — Compressor Motor
CR

Control Relay

D

Diode

EC

Enthalpy Control

EPS

Economizer Pressure Switch

EQUIP — Equipment
FPT

Freeze-Protection

Thermostat

GND

Ground

GVR

Gas Valve Relay

HPS

High-Pressure Switch

HS

Hall Effect Sensor

I

Ignitor

IDM

Induced-Draft Motor

IFC

Indoor (Evaporator) Fan

Contactor

IFM

Indoor (Evaporator) Fan Motor

IGC

Integrated Gas Unit

Controller

LED

Light Emitting Diode

LPS

Low-Pressure/Loss-of-Charge

Switch

LS

Limit Switch

MGV

Main Gas Valve

MTR

Motor

OAT

Outdoor Air Thermostat

OFM

Outdoor-Fan Motor

PL

Plug Assembly

QT

Quadruple Terminal

R

Relay

RS

Rollout Switch

SAT

Supply Air Thermostat

SEN

Sensor

TC

Thermostat-Cooling

TH

Thermostat-Heating

TRAN — Transformer

Field Splice

Marked Wire

Terminal (Marked)

Terminal (Unmarked)

Terminal Block

Splice

Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential
only, not to represent wiring

35

Advertising
This manual is related to the following products: