Attaching the ground wire – Dell Metered PDU LCD User Manual

Page 21

Advertising
background image

21

Installation

|

Attaching the Ground Wire

To attach the ground wire to the rack:

NOTE:

Dell recommends that you ground the rPDU to the rack frame with the ground wire provided in the Grounding Wire

Kit.

1

Connect one end of the ground wire to the ground bonding point location on the front panel of the rPDU
using the silver, 10-32

0.5” pan-head screw and star washer (supplied).

2

Connect the other end of the ground wire to a hole in the rack frame using the black, M5

12 pan-head

screw and star washer (supplied). See Figure 10.

Ground Bonding Point Connection

10-32

0.5” Pan-head Screw (Silver)

Star Washer

Frame Connection

M5

12 Pan-head Screw (Black)

Star Washer

Figure 10. Ground Bonding Point and Frame Connections

3

Continue to “Connecting Protected Equipment” on page 22.