Voltage command – Dell Metered PDU LCD User Manual

Page 64

Advertising
background image

64

|

Serial Interface Operation

voltage command

Use this command to retrieve the input voltage to the rPDU. The command response is specific to a single rPDU
and varies depending on whether the rPDU is a single-phase or three-phase model (see Table 16).

NOTE:

Voltage command query options cannot be used for single-phase rPDUs. However, query options can be used

with voltage command for three-phase rPDUs.

Table 16. Phase Line Nomenclature for Voltage Command

Voltage Nomenclature

1,2

Description

XN
RMS voltage between X and N

L1 Line to Neutral on a Wye-configured rPDU

YN
RMS voltage between Y and N

L2 Line to Neutral on a Wye-configured rPDU

ZN
RMS voltage between Z and N

L3 Line to Neutral on a Wye-configured rPDU

XZ
RMS voltage between X and Z

L1 Phase to Phase on a Delta-configured rPDU

XY
RMS voltage between X and Y

L2 Phase to Phase on a Delta-configured rPDU

YZ
RMS voltage between Y and Z

L3 Phase to Phase on a Delta-configured rPDU

1

Line-to-Neutral voltage will not be reported on a Delta-configured rPDU

2

Line-to-Line voltage will not be reported on a Wye-configured rPDU

Usage

rPDU>voltage [summary] [XN|YN|ZN|XZ|XY|YZ]]

where:

[summary]

= Retrieves a summary of voltage per phase for all three phases

[XN|YN|ZN|XZ|XY|YZ]

= Phase line (see Table 16)

Retrieve the present input voltage for rPDU phase lines

rPDU> voltage

Single-Phase Example

rPDU> voltage
rPDU: RMS voltage: 240V.

Three-Phase Wye Example

rPDU>voltage
rPDU: RMS voltage between X and N: 208V.
rPDU: RMS voltage between Y and N: 209V.
rPDU: RMS voltage between X and N: 207V.

Three-Phase Delta Example

rPDU>voltage
rPDU: RMS voltage between X and Z: 208V.
rPDU: RMS voltage between X and Y: 209V.
rPDU: RMS voltage between Y and Z: 207V.