Standard Protection Mechanisms

The cooling unit is programmed to shut down certain components to protect

those components, as well as the wine inside the cellar, under the following

circumstances:

Scenario

What it means

What happens

P1 Alarm

Probe 1, which senses the
temperature inside the cellar
and controls the on/off cycles
of the cooling unit, has failed

The cooling unit enters a
timed auto-cycle mode until
Probe 1 is repaired or
replaced. In this mode, the
cooling unit will turn on for
12 minutes and off for 8
minutes.

Scenario

What it means

What happens

HA2 Alarm

P3 > 140° F

The condenser probe is
measuring temperatures that
are too hot

The compressor and
condenser fan will turn off
until the condenser
temperature falls below
120°F