CAUTION

The drain pipe of indoor unit must be heat insulated, or it will
condense dew, as well as the connections of the indoor unit.

Hard PVC binder must be used for pipe connection, and make
sure there is no leakage.

Drainage test

Install the drain joint of the outdoor unit

Check whether the drainpipe is unhindered.

New built house should have this test done before
paving the ceiling.

With the connection part to the indoor unit, please be noted not
to impose pressure on the side of indoor unit pipes.

When the declivity of the drain pipe downwards is over 1/100,
there should not be any winding.

The total length of the drain pipe when pulled out traversely
shall not exceed 20m, when the pipe is over long, a prop stand
must be installed to prevent winding.

Refer to the Fig.8-1 for the installation of the pipes.

All the figures in this manual are for explanation purpose only.
They may be slightly different from the heat pump you
purchased.The actual unit shall prevail.

1.5m~2m

Insulating

material

Downward declivity

lower than 1/100

Bend

S shape

VP30

Downw ard declivity

lower t han 1/100

Put as deep as possible

(about 10cm)

Fig. 8-1

Seal

The base pan hole

of outdoor unit

Drain joint

Seal

The base pan

of outdoor unit

Drain

joint

Fig.8-2

NOTE

Outdoor unit is equiped with a drain piping. Its position is
shown figure below

Drain Piping

Fig.8-2

Fit the seal into the drain joint, then insert the drain joint into
the base pan hole of outdoor, rotate 90

0

to securely

assemble them. Connect the drain joint with an extension
drain hose (Locally purchased), in case of the condensate
draining off the outdoor unit during the heating mode.(Refer
to Fig.8-2)

Plug

75

Slope 2 %

Prepare a polyviny chloride with 21mm inner diameter

Connect a siphon, as shown in figure below

Fasten the tube to the drain hose with an adhesive and the
field-supplied clamp. The drain piping must be performed with
a DOWN-SLOPE pitch of 1/25 to 1/100

A B

18~24

595 1200

36

624 1381

48~60

646 1385

MODEL

Table 8-1

Fig.8-3

9. WIRING

The appliance shall be installed in accordance with
national wiring regulations.

The heat pump should use separate power supply with
rated voltage.

The external power supply to the heat pump should have
ground wiring, which is linked to the ground wiring of the
indoor and outdoor unit.

The wiring work should be done by qualified persons
according to circuit drawing.

unit:mm

An all-pole disconnection device which has at least 3mm
sepaaration distance in all pole and a residual current
device (RCD) with the rating of above 10mA shall be
incorporated in the fixed wiring according to the national
rule.

Be sure to locate the power wiring and the signal wring
well to avoid cross-disturbance.

Do not turn on the power until you have checked
carefully after wiring.

The power cord type designation is H07RN-F.