4

installation manual

Evaluate the ceiling construction and please install with

Ø

10

hanging screw bolts.

5.2 Install the main body(the unit with the
water pump is not included)

5.2.1 Wall Mounting Installtion

Fig. 5-2

C

D

B

Hook

E. Connecting point of

refrigerant pipe

(D. gas side)

D. Connecting point of

refrigerant pipe

(E. Liquid side)

Drain point

Fig.5-3

Fig.5-4

1 Fix the hook with tapping screw onto the wall.(Refer to Fig.5-3)

2

Hang the indoor unit on the hook.

(The bottom of body can touch with floor or suspended, but the
body must install vertically.)

D

Hook

Tapping

screw

Washer

<6

mm

5.2.2 Ceiling Installation

Fig.5-9

STEEL ROOF BEAM STRUCTRUE

Hanging screw bolt

Hanging

bolts

Supporting

angle steel

Install and use directly the supporting angle steel.

Please Refer to Fig.5-3 and Fig.5-4 for the hanging screw
bolts distance

The handling to the ceiling varies from the constructions,
consult the construction person for the specific condition.

Do keep the ceiling flat. Consolidate the roof beam

to avoid

possible vibration.

1 Installing Ø10 hanging screw bolts. (4 bolts)

After the selection of installation location, position the refrigerant
pipes, drain pipes,indoor & outdoor wires to the connection
places before hanging up the machine.

Cut off the roof beam.

Strengthen the place that has been cut off, and
consolidatethe roof beam.

The installation of hanging screw bolts.

Fig.5-5

Fig.5-6

Fig.5-7

Fig.5-8

WOODEN CONSTRUCTION

NEW CONCRETE BRICKS

FOR ORIGINAL CONCRETE BRICKS

Steel bar

Embedding screw bolt

(Pipe hanging and embedding screw bolt)

(Blade shape

insertion)

(Slide insertion)

Roof beam

Hanging screw bolts

Ceiling

Timber over the beam

Put the square timber traversely overthe roof beam, then install
the hanging screw bolts.

Inlaying or embedding the screw bolts.

Install the hanging hook with expansible bolt into the concrete
deep to 45~50mm to prevent loose.