3 address and termination switches, 4 led status indicators, X1 x10 – Rice Lake 920i Programmable HMI Indicator/Controller - Profibus DP Interface User Manual

Page 8

Advertising
background image

4

520/720i/820i/920i

Profibus DP Installation and Programming Manual

2.3

Address and Termination Switches

The Profibus Interface address and bus termination
are set using switches on the Profibus module.
Figure 2-6 shows the address and termination
switches.

Figure 2-6. Profibus Module Switches

Termination Switch

If the Profibus Interface is the first or last module on
the bus, set the termination switch ON. Otherwise, set
the switch OFF to disable bus termination.

Address Switches

Two rotary switches are used to set the decimal node
address, 1–99, of the Profibus Interface (Address 0 is
reserved.) Note that the node address cannot be
changed during operation.

The left switch shown in Figure 2-6, marked

x10

, sets

the tens digit; the right switch,

x1

, sets the units digit.

(For example, to set a decimal address of 14, set

x10 =

1,

and

x1 = 4

.)

2.4

LED Status Indicators

An LED array on the Profibus module provides status
information for troubleshooting. LEDs 2 and 3
provide status indication for the Profibus module;
LED 4 provides Profibus diagnostic information. LED
1 is reserved.

Figure 2-7. Profibus Status LED Module

Table 2-2 summarizes the function of the status LEDs.

A single bi-color LED on the surface of the Profibus
m o d u l e p r o v i d e s d i a g n o s t i c i n f o r m a t i o n f o r
debugging the module itself. Table 2-3 lists the
indications provided by the debugging LED.

x1

x10

Termination

switch

Address
switches

LED

Status

Description

LED 2
Online

Off

Not online

Steady Green

Module is online

LED 3
Offline

Off

Not offline

Steady Red

Module is offline

LED 4

Fieldbus

Diagnostics

Off

No diagnostics

Flashing Red,

1 Hz

Configuration error

Flashing Red,

2 Hz

User parameter data error

Flashing Red,

4 Hz

Initialization error

Table 2-2. Status LED Indications

Status

Description

Off

No power

Red, 4Hz

DPRAM check fault

Red, 2Hz

ASIC and FLASH ROM check fault

Red, 1Hz

RAM check fault

Green, 2Hz

Module not initialized

Green, 1Hz

Module initialized and running

Table 2-3. Debugging LED Indications

1

2

3

4

Fieldbus

diagnostics

Online

Offline