2 sealoff fittings, 8 el232 xcpd installation manual – Rice Lake EL232 XPCD Explosion Proof Remote Serial Display User Manual

Page 12

Advertising
background image

8

EL232 XCPD Installation Manual

2.2

Sealoff Fittings

The utmost care must be taken to completely seal the inside of the remote display off from the outside world. To
do this all wiring into and out of the enclosure must be in conduit using sealoff fittings between the remote
display and the conduit. The sealoff fittings ensure that the hazardous atmosphere does not travel either through
the conduit or through insulation or wiring back to the safe area. The graphic shown below illustrates the location
of sealoff fittings.

These fittings, once installed and sealed are very difficult to remove so make sure all the wiring has been double
checked before beginning. If rigid conduit is not being used for connection to the scale base, be sure to install an
approved strain relief fitting to avoid pulling the wires out of the sealoff fittings in an accident. Doing so would
open a flame path to the enclosure and defeat its purpose.

Note:

The inside of an explosion proof enclosure is considered a Division II area when the enclosure has

been properly sealed.

SEAL FITTING

18" MAX.

FROM BOX

MAKE SURE THE MOUNTING SUPPORT IS CAPABLE
OF HOLDING CONDUIT TIGHT AGAINST IT. NO
STRAIN MUST BE PLACED ON THE SEALOFF
FITTING ASSEMBLY.

WHEN USING FLEXIBLE CONDUIT, USE
MULTIPLE PIPE STRAPS TO SECURE
R I G I D C O N D U I T T O T H E S U P P O R T
STRUCTURE. ATTACH THE FLEXIBLE
CONDUIT TO THE RIGID CONDUIT ONLY
AFTER MULTIPLE STRAPS HAVE BEEN
ATTACHED TO PREVENT ANY STRAIN
FROM REACHING THE SEAL-OFF FITTINGS.

CLASS I

DIVISION 2

GROUP

C & D

CLASS II

DIVISION 1

GROUP

E F & G

TO

PREVENT IGNITION OF

HAZ.

ATMOS.,

DISCONNECT

ORE OPENING

. KEEP

CIRCUIT IS

ALIVE

FROM SUPPL

Y BEF

ASS'Y TIGHT WHILE

CA

UTION:

REMOTE WEIGHT DISPLAY

LBS

KGS

GROSS

NET

NO SIGNAL

MADE IN U.S.A.