The design intent of an explosion proof enclosure is not to contain an explosion, but to control it. The flame
path is carefully controlled at the flanges. This insures that if an explosion occurs, any gases that escape will
be cooled to a temperature below the ignition point of any atmosphere specified within that enclosure’s
rating.

Explosion

HAZARDOUS

AREA

High temperature

gases

Cooling from

expansion of gas

(Boyle’s Gas Law)

The distance from the boundary of

the inside of the enclosure to the

gasket is known as the Flame Path.

This distance must be at least 1" for

Group C throughG.

INSIDE OF

ENCLOSURE

Lower

temperature

gases

Enlarged view

below

Propagation of gas due to

pressure from an internal

explosion

Gasket

For clarity, the slope of the flange
faces has been greatly enhanced

(Typically, the slope is .0015"/inch)