Grounding

Rice Lake Weighing Systems strongly recommends installation of the RailBoss grounding system to protect the
RailBoss Railroad Track Scale from surges. Rail track scales of all types can be exposed to surges or lightning that
may hit the rail at even very long distances from the scale. It is recommended that scale sections be isolated from
the rail track on both ends of each section. Eight-foot ground rods should be driven between the rails, and a copper
wire connected to the rail on each side with a 10-gauge copper wire. Rail joint bar isolators (included) should also
be installed at each end of RailBoss sections.

Replacement Part Numbers

Table 4-1. Rail Joint Bar Isolator Kits

Part Number

Description

126111

Rail Joint Bar Isolator kit, 90 RE Full or Double Draft

112702

Rail Joint Bar Isolator kit, 115 RE Full or Double Draft

119771

Rail Joint Bar Isolator kit, 132 RE Full or Double Draft

Table 4-2. Grounding Kit Part Numbers

Part Number

Description

Grounding Kit Contents (Qty)

119800

Grounding kit, 115 lb RE Double Draft

110812, UPS Sola S1K520, (1)
119913, 8’ Copper bonded steel ground rod (2)
119916, Ground rod clamp (2)
119917, Pipe clamp, grounding (4)
119920, Copper wire, 10 ga. 25’ (1)

119801

Grounding kit, 115 lb RE Full Draft

119802

Grounding kit, 132 lb RE Double Draft

119803

Grounding kit, 132 lb RE Full Draft

4.1

Ground Rod Locations

Ground rod placement can vary depending on ground hardness; however, 8

'

ground rods should be installed near

the center of the track. See Figure 4-1 and 4-2 for recommended ground rod locations.

Ground rod

Isolators

Isolators

Figure 4-1. Ground Rod Locations in Double-Draft System

Ground rod

Isolators

Isolators

Figure 4-2. Ground Rod Locations in Full-Draft System