Ydo01m-io, option a5: specifications, Ydo01m-en (option b9) – Rice Lake Sartorius Midrics 1 and 2 Series - Installation Instructions User Manual

Page 10

Advertising
background image

10

Example: Basic Circuit Diagram

YDO01M-IO, Option A5:
Specifications

Digital inputs

– Quantity: 5
– Low level:

–3 V to +5 V

– High level:

+11 V to +30 V

– Maximum current

consumption:

2.6 mA at 15 V

– Inputs are activated by applying

the corresponding voltage.

Digital outputs

– Quantity: 5
– Maximum current flow per channel:

100 mA

– Voltage range:

0–30 VDC

– Each output is formed

by an opto-electronic coupler.

YDO01M-EN (Option B9)

Equipment Supplied

– YDO01M-EN interface module
– Operating instructions (this document)
– Interface description (fieldbus for

TCP Modbus)

Assembly
Connect interface module YDO01M-EN
(Ethernet interface) directly to the digi-
tal board of the scales without configu-
ration. For more information, please
refer to chapter entitled “Installing Data
Output Ports in the Indicator”.
Insert the YCC02RJ45M7 plug on the
Sartorius Ethernet cable (option M38)
into the port of the interface module.

Note:

!

Only use cables and plugs that conform
to the Ethernet specification (CAT5 or
better):
Ethernet cable with Sartorius order no.
YCC02RJ45M7 (Option M38) cable
gland
Use the interface module only with the
following devices:

– Indicator MIS1, MIS2 (IP65)
– Complete scales MW1, MW2 (IP65)

OUTx_high

30V

0.2A

LV1

LV1

OUTx_low

1

2

3

4

Inputx_high

1

2

3

4

LV2

LV2

Inputx_low

Advertising