Setting Baud Rate / Selecting Device Type (For switch locations see Figure C3.)

DIP switches SW3-1 through SW3-6 are used to set the desired baud rate for the RS232 device. SW3-7 and
SW3-8 are used to select the RS232 device the DNA100 is driving (see chart below).

BAUD

RATE

SW3

DEVICE

SW3

1

2

3

4

5

6

7

8

19200

1

0

0

0

0

1

Terminal

0

0

9600

1

0

0

0

1

0

0 = off

Printer

0

1

4800

0

1

0

0

0

1

1 = on

Not used

1

0

2400

0

1

0

0

1

0

Not used

1

1

1200

1

0

0

0

1

1

Communication Protocols

Aside from the baud rate, the terminal emulation should be set for VT100.
The DNA100 has No Parity, 8 Data Bits, and 1 Stop Bit.

Hardware flow control is used (RTS/CTS). The DNA100 will send data only if CTS is high from the other device.

Compatible emulation software:
Procomm Plus
Terminal
for Windows 3.11
Hyper Terminal for Windows 98/XP

Set software flow control to OFF and hardware flow control to ON.
Set Pace character to >