Smart Power Systems HR-110 User Manual

Page 34

Advertising
background image

Smart Power

®

Systems

A. C. MODULAR GENERATOR SYSTEM

Page 33 of 53

e.

. If the system measures an output voltage that is too low or too high
the generator will automatically shut down in 30 minutes unless the shutdown is
overridden.

f.

. If the system detects a faulty temperature sensor, the generator will
automatically shut down in 30 minutes unless the shutdown is overridden.

g.

. If the oil filter service warning is ignored, and the oil filter is not
changed following the procedure outlined in the “Maintenance Instructions”
section of this manual, the generator will automatically shut down in 30 minutes
unless the shutdown is overridden.

WARNING:


Overriding an automatic system shutdown may result in permanent damage to the
system and/or degrade the system’s performance.

Overriding an automatic system shutdown may void warranty. The system’s
electronic controller records whenever an override function is performed. Always
avoid overriding a shutdown if possible.


9.

The following is an example of how an automatic shutdown can be overridden.
This example describes how to override an OIL HOT shutdown, but the override
procedure is the same for all the above listed diagnostic faults:


Step a: Press Mode to
cause  and the  and
 labels to appear.

Step b: Press On/Off to
answer “yes” and make
the next screen appear.

Example of Command & Control Center in hot oil fault override

Figure 22


a. From the Normal mode display, press Mode, as if you wanted to display the oil

temperature. The screen shown in Figure 22 will be displayed instead, asking if
you want to “

.” This screen will also be displayed if you attempt to start

the generator with the condition present.

Advertising
This manual is related to the following products: