Page 47 of 50


2.

Adjust pump compensator:

a. Reference Figure 30.

b. Loosen the flow control pressure jam nut.

c. While monitoring the generator’s output voltage, slowly rotate the flow control

set screw with a 4mm hex wrench. Adjust the flow control until the generator’s
output frequency is 63 Hz.


d. While keeping the setscrew from rotating, with the hex wrench, re-tighten the

jam nut.

Pump assembly

Figure 30