F. DRIVE SYSTEM SOFT START

The DI-225 dryer is equipped with either a Series 154-A11NB OR 21B or 25 soft start control.

ALL soft start controls are factory preset. Re-adjustment should not be necessary

1. Series 154-A11NB OR 21B Drive System Soft Start

Wiring

The Series 154-A11NB OR 21B is a motor controller and is used with an electromechanical

motor starter. The controller is wired after the motor starter as shown in the illustration below.

The output side of the motor starter should be wired to the line terminals on the controller,

(L1,L2,L3). The load terminals on the controller, (T1,T2,T3) then Should be wired to the motor.

When the motor starter is turned on, 3-phase (3 ) power will be applied to the input to the

controller. The controller will then ramp up the voltage to the motor.The duration of the ramp will

depend on the setting of the soft start adjustment. When the motor starter is turned off, the

controller will reset and will be ready for the starter to be turned on again.

NOTE: THE STARTER MUST REMAIN OFF FOR A MINIMUM OF

½ SECOND TO ALLOW

THE CONTROLLER TO COMPLETELY RESET IF THE STARTER IS TURNED ON

BEFORE THE CONTROLLER RESETS, AN ACCEPTABLE SOFT START MAY BE

ACHIEVED.