Montage, Inbetriebnahme, Installation – Pilz S1UM 230-240VAC UM 0.1-500VAC/DC UP User Manual

Page 3: Operation, Mise en oeuvre

Advertising
background image

- 3 -

Fig. 2: Funktionsdiagramm/

Pulse diagram/
Diagramme fonctionnel

U

M

U

ab

U

an

12

12

LED

Y2

Y3

Y2

Y3

Y1

Y2

Y1

Y2

11

11

Arbeitsstromprinzip/

de-energised mode/

mode excitation

Ruhestromprinzip/

energised mode/

mode retombée

nicht speichernd/non-latching/non mémorisé

speichernd/latching/mémorisé

Arbeitsstromprinzip/

de-energised mode/

mode excitation

14

14

11

11

t

R

IIb

Ib

t

R

Ia

IIa

t

R

t

R

t

R

III

Hysterese (U

ab

): 0,8 x U

an

einstellbare Hysterese

t

R

: Reaktionszeit

Ia: U

M

> U

an

: nach Ablauf von t

R

zieht das

Relais an und die LED "OUT" leuchtet.
U

M

< U

ab

: Relais fällt ab und LED

erlischt

Ib: U

M

> U

an

: wie oben, aber Relais fällt ab

und LED "Out" erlischt
U

M

< U

ab

: Relais zieht an und LED

leuchtet

IIa: U

M

> U

an

vor Ablauf von t

R

: Relais bleibt

abgefallen

IIb: wie oben, aber Relais bleibt angezogen
III: U

M

> U

an

: s. oben

U

M

< U

ab

: Relais fällt erst ab, wenn

Y2-Y3 geöffnet ist.

Montage

Das Gerät muss in einen Schaltschrank mit
einer Schutzart von mind. IP54 eingebaut
werden. Zur Befestigung auf einer Norm-
schiene hat das Gerät ein Rastelement auf
der Rückseite.

Inbetriebnahme

Beachten Sie bei der Inbetriebnahme:
• Der Ausgangskontakt 11-12-14 ist ein

Hilfskontakt (z. B. für Anzeige oder
Schützansteuerung).

Vor den Ausgangskontakt eine Siche-

rung (6 A flink oder 4 A träge) schalten,
um das Verschweißen des Kontaktes zu
verhindern.

• Leitungsmaterial aus Kupferdraht mit

einer Temperaturbeständigkeit von
60/75 °C verwenden.

• Das Anzugsdrehmoment der Schrauben

auf den Anschlussklemmen darf max.
0,6 Nm betragen.

• Angaben im Kapitel "Technische Daten"

unbedingt einhalten.

Installation

The unit must be panel mounted (min.
IP54). There is a notch on the rear of the
unit for DIN-Rail attachment.

Operation

Please note with operation:
• The output contacts 11-12-14 is an

auxiliary contact (eg. for signalling or
contactor control)

• To prevent contact welding, a fuse

(6 A quick or 4 A slow) must be
connected before the output contacts

• Use copper wires that can withstand

temperatures of 60/75 °C .

• Tighten terminals to a max. 0.6 Nm
• Important details in the section “Technical

Data” should be noted and adhered to

Hysteresis (U

ab

): 0.8 x U

an

hysteresis can be set within this range
t

R

: reaction time

Ia: U

M

> U

an

: after t

R

has elapsed the

relay energises and the LED “OUT” is
illuminated.

U

M

< U

an

: as above, but the relay de-

energises and the LED “OUT” goes out.
Ib: U

M

> U

an

: as above, but the relay de-

energises and the LED “OUT” goes out

U

M

< U

ab

: relay energises and the LED

is illuminated

IIa: U

M

> U

ab

before t

R

has elapsed: relay

stays de-energised
IIb: as above but the relay remains energised
III: U

M

> U

an

: see above

U

M

< U

ab

: relay de-energises if Y2-Y3 is

open

Mise en oeuvre

Remarques préliminaires :
• Le contact de sortie 11-12-14 est un

contact d'information (ex. pour
signalisation ou pilotage de relais).

• Protéger les contacts de sortie par des

fusibles (6 A rapides ou 4 A normaux)
pour éviter leur soudage

• Le couple de serrage sur les bornes de

raccordement doit être d'au max. 0,6 Nm.

• Utiliser des câbles en cuivre supportant

des températures de 60/75°C

• Respecter les données indiquées dans le

chapitre „Caractéristiques techniques“.

Hystérésis (U

ab

): 0,8 x U

an

hystérésis réglable

t

R

: temps de réponse

Ia: U

M

> U

an

: au bout du temps t

R

, le relais

monte et la LED "OUT" est allumée.
U

M

< U

ab

: le relais retombe et la LED

s'éteint.

Ib: U

M

> U

an

: idem, mais le relais retombe et

la LED "Out" est éteinte.
U

M

< U

ab

: le relais monte et la LED

est allumée.

IIa: U

M

> U

an

avant fin de t

R

: le relais reste

au repos

IIb: idem, mais le relais reste excité
III: U

M

> U

an

: voir ci-dessus

U

M

< U

ab

: le relais retombe uniquement

si Y2-Y3 est ouvert.

Montage

Le relais doit être installé dans une armoire
ayant un indice de protection IP54. Sa face
arrière permet un montage sur rail DIN.