Installation, Wiring – Pilz PNOZ s3 C 24VDC 2 n/o User Manual

Page 5

Advertising
background image

PNOZ s3

Operating Manual PNOZ s3
21395-EN-10

5

}

Manual start: Unit is active once the input circuit is closed and then the start circuit is

closed.

}

Monitored start with falling edge: Unit is active once

– the input circuit is closed and then the start circuit is closed and opened again.
– the start circuit is closed and then opened again once the input circuit is closed.

}

Monitored start with rising edge: Unit is active once the input circuit is closed and

once the start circuit is closed after the waiting period has elapsed (see technical de-
tails).

}

Start with start-up test: The unit checks whether safety gates that are closed are

opened and then closed again when supply voltage is applied.

}

Increase in the number of available instantaneous safety contacts by connecting con-

tact expander modules or external contactors/relays;
A connector can be used to connect 1 PNOZsigma contact expander module.

Installation

Install base unit without contact expansion module:

}

Ensure that the plug terminator is inserted at the side of the unit.

Connect base unit and PNOZsigma contact expansion module:

}

Remove the plug terminator at the side of the base unit and at the contact expansion

module.

}

Connect the base unit and the contact expansion module to the supplied connector be-

fore mounting the units to the DIN rail.

Installation in control cabinet

}

The safety relay should be installed in a control cabinet with a protection type of at least

IP54.

}

Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).

}

When installed vertically: Secure the unit by using a fixing element (e.g. retaining brack-

et or end angle).

}

Push the device upwards or downwards before lifting it from the DIN rail.

Wiring

Please note:

}

Information given in the "Technical details" must be followed.

}

The outputs 13-14, 23-24 are safety contacts.

}

Semiconductor output Y32 should

not be used for safety circuits!

}

To prevent contact welding, a fuse should be connected before the output contacts (see

technical details).