Status indicators

Power

Supply voltage is present.

In1

Input circuit at S12 is closed.

In2

Input circuit at S22 is closed.

Out

Safety contacts are closed and semiconductor output Y32 carries a high signal.

Reset

24 V DC is present at S34.

Error indicators

All LEDs off

Diagnostics: Short across contacts/earth fault; unit switched off

}

Remedy: Rectify short across contacts/earth fault, switch off supply voltage

for 1 min.

Fault

Diagnostics: Plug terminator not connected

}

Remedy: Insert plug terminator, switch supply voltage off and then on

again.

Fault

Diagnostics: Internal error, unit defective

}

Remedy: Switch supply voltage off and then on again, change unit if neces-

sary.

Power

Diagnostics: Supply voltage too low

}

Remedy: Check the supply voltage.

In1, In2 alternately

Fault

Diagnostics: Short detected between S12 and S22

}

Remedy: Rectify short across contacts, switch supply voltage off and then

on again.