Preparing for operation, Operating modes, Set operating modes – Pilz PNOZ s3 C 24VDC 2 n/o User Manual

Page 6

Advertising
background image

PNOZ s3

Operating Manual PNOZ s3
21395-EN-10

6

}

Calculation of the max. cable length l

max

in the input circuit:

R

lmax

R

l

/ km

I

max

=

R

lmax

= max. overall cable resistance (see technical details)

R

l

/ km = cable resistance/km

}

Use copper wire that can withstand 60/75 °C.

}

Sufficient fuse protection must be provided on all output contacts with capacitive and in-

ductive loads.

}

When connecting magnetically operated, reed proximity switches, ensure that the max.

peak inrush current (on the input circuit) does not overload the proximity switch.

Preparing for operation

Operating modes
The operating mode is set via the rotary switch on the unit. You can do this by opening the
cover on the front of the unit.

CAUTION!
Do not adjust the rotary switch during operation, otherwise an error mes-
sage will appear, the safety contacts will open and the unit will not be ready
for operation until the supply voltage has been switched off and then on
again.

Set operating modes

}

Switch off supply voltage.

}

Select operating mode via the operating mode selector switch "mode".

}

If the operating mode selector switch "mode" is in its start position (vertical position), an

error message will appear.

Operating mode

selector switch

"mode"

Automatic/man-

ual start

Monitored start

rising edge

Monitored start

falling edge

Automatic start

with start-up test

Without detec-

tion of shorts

across contacts

In2-

In2+

In2-

In2+

In2-

In2+

In2-

In2+

With detection of

shorts across

contacts

In2-

In2+

In2-

In2+

In2-

In2+

In2-

In2+