6-32

T-268-07

NOTE

If the condenser cooling water is not being used
as drinking water or is not re-circulated in a
closed or tower system, neutralizing is not

necessary.

11. Put the unit back in service and operate under

normal load. Check the head pressure. If normal, a

thorough de-scaling has been achieved.

What You Can Do For Further Help:
Contact the Engineering and Service Department of the
OAKITE PRODUCTS CO., 19 Rector Street, New

York, NY 10006 U.S.A. for the name and address of the
service representative in your area.

Fill condenser with

cleaning solution. Do

not add solution more

rapidly than vent can

exhaust gases caused

by chemical action.

Condenser

Vent

pipe

1” Pipe

5’ Approximate

3’ to 4’

Figure 6-33. Water-Cooled Condenser Cleaning --

Gravity Circulation

Table 6-1. AMBS, DTS, RRS, RTS, SRS and STS

Temperature-Resistance Chart

Temperature

Centigrade

Temperature

Fahrenheit

Resistance

(Ohms)

RRS, RTS, SRS and STS:

0

32

32,650 91

25

77

10,000 50

AMBS and DTS

0

32

32,650 +1720

-- 1620

25

77

10,000 + 450

-- 430

Table 6-2. Partlow Bulb Temperature-Resistance

Chart

TEMPERATURE

RESISTANCE

_

_

_

_

F

_

_

_

_

C

(OHMS)

--10

--23.3

12561.00

--5

--20.6

10579.70

0

--17.8

8944.17

5

--15.0

7588.89

15

--9.4

5520.32

20

--6.7

4731.71

25

--3.9

4068.68

30

--1.1

3509.36

32

0

3310.57

35

1.7

3035.99

40

4.4

2634.10

45

7.2

2291.85

50

10.0

1999.52

55

12.8

1749.11

60

15.6

1534.00

65

18.3

1348.72

75

23.9

1050.14

80

26.7

929.87

85

29.4

825.21

90

32.2

733.93

95

35.0

654.12

100

37.8

584.19

105

40.6

522.79