Table 3-4. Controller Alarm Indications

CODE

#

TITLE

DESCRIPTION

MODEL 69NT40-511-72

AL11 Evaporator Fan

Motor 1 Safety

Alarm 11 is triggered by the opening of the internal protector for evaporator fan

motor #1. This alarm will disable the probe check portion of defrost and the probe

diagnostic logic.

AL12 Evaporator Fan

Motor 2 Safety

Alarm 12 is triggered by the opening of the internal protector for evaporator fan

motor #2. This alarm will disable the probe check portion of defrost and the probe

diagnostic logic.

ALL MODELS

AL20 Control Circuit Fuse

Open (24 vac)

Alarm 20 is triggered by fuse (F3) opening and will cause the software shutdown

of all control units. This alarm will remain active until the 15 amp fuse is replaced.

AL21 Micro Circuit Fuse

Open (18 vac)

Alarm 21 is triggered by one of the fuses (F1/F2) being opened on 18 volts AC

power supply to the Controller. The suction modulation valve (SMV) will be

opened and current limiting is halted. The compressor will cycle. Temperature

control will be maintained by cycling the compressor.

AL22 Evaporator Fan

Motor Safety

Alarm 22 is triggered by the opening of the evaporator motor internal protector.

This alarm will disable all control units until the motor protector resets. Also, refer

to code Cd29.If the unit is configured for single evaporator fan operation, alarm

AL22 will also activate if alarms AL11 and AL12 are active simultaneously.

AL23 KA2--KB10 Jumper

Disconnected

Alarm 23 is triggered by a missing jumper wire. The alarm will stay active until the

jumper wire is reconnected.

AL24 Compressor Motor

Safety

Alarm 24 is triggered by the opening of the compressor motor internal protector.

This alarm will disable all control units except for the evaporator fans and will

remain active until the motor protector resets. Also, refer to code Cd29.

AL25 Condenser Fan

Motor Safety

Alarm 25 is triggered by the opening of the condenser motor internal protector

and will disable all control units except for the evaporator fans. This alarm will

remain active until the motor protector resets. This alarm is deactivated if the unit

is operating on water cooled condensing.

AL26

All Supply and

Return Air Control

Sensors Failure

Alarm 26 is triggered if the Controller determines that all of the control sensors

are out-of-range. This can occur for box temperatures outside the range of --50_C

to +70_C (--58_F to +158_F). This alarm triggers the failure action code set by

Function Code Cd29.

AL27 Probe Circuit

Calibration Failure

The Controller has a built-in Analog to Digital (A-D) converter, used to convert

analog readings (i.e. temperature sensors, current sensors, etc.) to digital

readings. The Controller continuously performs calibration tests on the A-D

converter. If the A-D converter fails to calibrate for 30 consecutive seconds, this

alarm is activated.This alarm will be inactivated as soon as the A-D converter

calibrates.

AL51 Alarm List Failure

During start-up diagnostics, the EEPROM is examined to determine validity of its

contents. This is done by testing the set point and the alarm list. If the contents

are invalid, Alarm 51 is activated.During control processing, any operation

involving alarm list activity that results in an error will cause Alarm 51 to be

activated.Alarm 51 is a “display only” alarm and is not written into the alarm list.

Pressing the ENTER key when “CLEAr” is displayed will result in an attempt to

clear the alarm list. If that action is successful (all alarms are inactive), Alarm 51

will be reset.

AL52 Alarm List Full

Alarm 52 is activated whenever the alarm list is determined to be full; at start-up

or after recording an alarm in the list. Alarm 52 is displayed, but is not recorded in

the alarm list. This alarm can be reset by clearing the alarm list. This can be done

only if all alarms written in the list are inactive.