P8-1 Perishable Mode

Pull Down Test

Requirements: Control temperature must be at least 60_F.

Setup: The set point is changed to 32_F, and a 180 minute timer is started. The

left display will read “P8-1,” the right display will show the supply air temperature.

The unit will then start to pull down the container temperature to the 32_F set

point.

Pass/Fail Criteria: The test passes if the container temperature reaches set

point before the 180 minute timer expires.

P8-2

Perishable Mode

Maintain

Temperature Test

Requirements: Test P8-1 must pass for this test to execute.

Setup: The left display will read “P8-2,” and the right display will show the supply

air temperature. A 60 minute timer is started. The unit will be required to

maintain the 32_F temperature to within + or -- 0.5_C (0.9_F) of set point until a

DataCORDER recording is executed. The recorder supply probe temperature

running total (and its associated readings counter) will be zeroed out for the

remainder of the recording period at the start of this test, so that the actual value

recorded in the DataCORDER will be an average of only this test’s results. Once

a recording interval is complete, the average recorder supply temperature will be

recorded in the DataCORDER, as well as stored in memory for use in applying

the test pass/fail criteria.

Pass/Fail Criteria: If the recorded temperature is within +/-- 0.5_C. of set point

from test start to DataCORDER recording, the test passes. If the average

temperature is outside of the tolerance range at the DataCORDER recording, the

test fails.

P9-0 Defrost Test

Setup: The defrost temperature sensor (DTS) temperature will be displayed on

the left display. The right display will show the supply air temperature. The unit

will run FULL COOL for 30 minutes maximum while the DTS sensor temperature

is above 10_C. Once the DTS is below 10_C, the unit simulates defrost by

running the heaters for up to two hours, or until the DTS senses the temperature

above 25.6_C.

Pass/Fail Criteria: The test passes if DTS is sensed above 25.6_C before a two

hour timer times out. The test fails if DTS does not go below 10_C after 30

minutes of full cooling, and/or the heater termination thermostat (HTT) is open

when the DTS is below 10_C. The test also fails if the HTT opens anytime during

the defrost cycle and/or the return air temperature exceeds 120_F anytime

during the heat cycle.

P10-0 Frozen Mode

(Setup) Test

Setup: After completion of the DTS test, the set point will be set to 7_C (45_F).

The left display will read “P100,” and if the container temperature is below 45_F,

will continue this display until the container temperature is raised to set point.

The left display will change to “P101” and execute the frozen pull down test

when the container temperature reaches set point, or if the container

temperature initially was greater than or equal to set point. The maximum time

allowed in heat mode is one hour.

Pass/Fail Criteria: If this time limit is exceeded, the test fails. There will be no

pass indication for this test. However, if the test fails the display will read “P100,”

“FAIL.”