Before starting any procedures listed below, check room thermostat and circuit breaker settings.

Note: For cross reference to number coded components, see figure 7.

F. ROOM UNIT TROUBLESHOOTING GUIDES

Check wall thermostat for

possible miscalibration

Check voltage across F1 & F2 terminal

block positions (24).

NO VOLTAGE PRESENT

VOLTAGE PRESENT

Check wall thermostat and/or

field wiring.

Check voltage across fan high limit

switch terminals (56).

NO VOLTAGE PRESENT

VOLTAGE PRESENT

Replace fan limit switch (56).

Remove fan assembly (47) and check

voltage to fan motor(s) (53).

NO VOLTAGE PRESENT

VOLTAGE PRESENT

Check fan impeller for debris that

could cause jamming. Replace if

necessary.

Check units internal

wiring.

Set wall thermostat to high

stop position.

FAN(S) DO NOT OPERATE.

FAN(S) NOW OPERATE.

Model: S Series Only

Function: Air Delivery

Problem: Fan(s) do not operate.