Unit discharges improperly.

FANS RUN

INTERMITTENTLY

DISCHARGE
AIR
TOO WARM

DISCHARGE AIR
TOO COOL

Check for damper jamming and

bimetallic coil assembly (39)

calibration.

Check bimetallic coil

assembly (39) for proper

calibration (see note).

PROBLEM WITH
CORE CHARGING

See Core Charging, Unit

Will Not Charge, flow

chart to troubleshoot.

PROBLEM
PRESENT

OK

Install damper clearancing

bracket, Steffes ETS item

#1140209

If problem persists, replace fan

high limit switch (56).

NOTE: To test the bimetallic coil assembly, it must
be completely cold. Either allow room unit to cool
completely or remove fan assembly and cool to
room temperature. Once the coil is cold, disconnect
the damper linkage and let the bimetallic coil go to
its relaxed position. The bimetallic coil on units
equipped with air deflectors should be calibrated at
a 90

o

angle from the front of the fan assembly. The

bimetallic coil of units not equipped with an air
deflector are calibrated at a 65

o

angle from the front

of the fan assembly. Use the cutout gauge on the left
for checking this calibration. (To determine whether
the unit is equipped with an air deflector, these
deflectors would be located in fan assembly behind
bimetallic coil.)

Check unit for proper

amperage draw.

Repair or replace fan

assembly (47).

PROBLEM

PRESENT

OK

Recalibrate bimetallic coil

assembly (39), or repair or

replace fan assembly (47).

Model: S Series Only

Function: Air Delivery

Problem: Improper Air Discharge.

Before starting any procedures listed below, check room thermostat and circuit breaker settings.

Note: For cross reference to number coded components, see figure 7.

Check for damper

jamming or obstruction.

Check for adequate

core temperature

OK