Check for line voltage between L1 and L2

terminal block positions (24).

VOLTAGE

PRESENT

VOLTAGE PRESENT

CHARGE
CONTROL
CIRCUIT
UNUSED

Check for voltage between L1 and T1

terminal block positions (24).

Recheck charge control thermo-

stat (45) setting and/or replace

thermostat.

NO VOLTAGE

PRESENT

NO VOLTAGE PRESENT

Model: S Series Only

Function: Core Charging

Problem: Unit will not charge.

With charge control thermostat (45)

in highest position, check for line

voltage between A1 and A2 terminal

block positions (24).

VOLTAGE
PRESENT

Troubleshoot and repair load

management control or field wiring.

VOLTAGE PRESENT

(Service light on.)

Replace core charging high limit

switch (33).

Check for line voltage between L2 and T2

terminal block positions (24), or observe

service light for illumination (50).

NO VOLTAGE PRESENT

(Service light off.)

Troubleshoot and repair field

wiring.

NO
VOLTAGE
PRESENT

Check unit wiring and heating

elements (54).

Before starting any procedures listed below, check room thermostat and circuit breaker settings.

Note: For cross reference to number coded components, see figure 7.