Modbus-rtu (over rs-485), Wiring pinout, Modbus setup – Hardy HI 6300 Series User Manual

Page 39: Wiring pinout modbus setup

Advertising
background image

Network Configuration 31

Modbus-RTU (over RS-485)

Step 1. Setup a slave address assigned to the HI 6300 series instrument from the

communications menu and the Modbus-RTU submenu.. Use a unique address
between 1 and 247

Step 2. Set the Baud Rate to the same as the master device, typically 9600 or 19,200

Step 3. Set the Parity Bit parameter to match that of the Modbus-RTU master (EVEN,

ODD, or OFF)

Wiring Pinout

The RS 485 serial port pinout is:

Modbus Setup

Slave Address may be set to any number in the range of 1-247.

Set Baud Rate parameter to match the settings of the Modbus master

Set Parity to match the settings of the Modbus master

Pin 1

Pin 2

Pin 3

Pin 4

Pin 5

Pin 6

Ground

TX+

TX-

RX+

RX-

Shield