Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 16

Advertising
background image

GF-114

MODBUS

Communication

Chapter 2

OMM-0035_0C

USER MANUAL

Standard Register Assignments

Page

16 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Table 2-1: C-More Boiler Controller Standard Input Register Address Mapping

(Continued)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

29 (0x001D)

Sensor Log

Outlet Temp

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

30 (0x001E)

Sensor Log

Inlet Temp

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

31 (0x001F)

Sensor Log

FFWD Temp

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

32 (0x0020)

Sensor Log

Exhaust Temp

DEGREES_3 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

33 (0x0021)

Sensor Log

Outdoor Temp

DEGREES_2 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

34 (0x0022)

Sensor Log

Aux Temp

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

35 (0x0023)

Sensor Log

CO xmitter

PPM_UNITS

36 (0x0024)

Sensor Log

O2 xmitter

% (0 to 100)

37 (0x0025)

Sensor Log

Flow Meter

GPM_UNITS

38 (0x0026)

Time Log

Status

73 (“I”) = Ignition

74 (“O”) = Off

80 (“P”) = Power Up

82 (“R”) = Run

39 (0x0027)

Time Log

Fire Rate

% (0 to 100)

40 (0x0028)

Time Log

Flame Strength

% (0 to 100)

41 (0x0029)

Time Log

Run Length

Int (0 to 65535)

42 (0x002A)

Time Log

Date

Int (0 to 65535)

1 count/day

43 (0x002B)

Time Log

Time

Int (0 to 1439)

1 count/min.

Advertising