MODBUS

Communication

GF-114

Hardware Setup & Installation

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

65 of 200
















Figure 4-7: I/O Box RS485 COMM Terminal Connections

Connect 120 OHM, 1/2

Watt resister between

+ and – RS485

terminals on the LAST

C-More Box.

I/O PC
Board

NOTE

Do not terminate the shields

of the RS485 leads to the

ground (GND) terminal. The

shields must be terminated

at the source ends only.

Connect the shields of the

incoming and outgoing

RS485 leads together.