Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 20

Advertising
background image

GF-114

MODBUS

Communication

Chapter 2

OMM-0035_0C

USER MANUAL

Standard Register Assignments

Page

20 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Table 2-2: C-More Controller Standard Holding Register Address Mapping

(Continued)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Comments

67 (0x0043)

Sensor Log Interval

Enum (0 to 8)

0 = Off

1 = 1 Min.

2 = 5 Min.

3 = 15 Min.

4 = 30 Min.

5 = 1 Hr.

6 = 6 Hrs

7 = 12 Hrs.

8 = 24 Hrs.

Default = 4 (30 min)

68 (0x0044)

Fault Log Pointer

int 0 - 9

69 (0x0045)

Sensor Log Pointer

int 0 - 1199

70 (0x0046)

Time Log Pointer

int 0 - 10239

71 (0x0047)

Thru

65535 (0xFFFF)

(Reserved)

Available for future

expansion.