CHAPTER 6. MODBUS SOFTWARE SETUP: C-MORE &

BMS II/ACS

NOTE

Section 6 provides Modbus Software Setup information for BMS II

and ACS units only. Refer to Section 5 for Modbus Software Setup

information for BMS (Model 168) units.

NOTE

The BMS II/ACS includes a Modbus Pass-Thru function which

permits an EMS to monitor and configure the boilers on the

Modbus network. However, it does not permit the EMS to directly

control the boilers. This Modbus Pass-Thru feature is enabled in

the BMS II/ACS RS232 Menu. Refer to BMS II Manual GF-124 or

ACS Manual GF-131, paragraph 3.6, and Appendix A for details.

6.1 INTRODUCTION

This Section provides the information necessary to configure the AERCO C-More Boiler

Controllers and a Boiler Management System II (BMS II)/AERCO Control System (ACS) for

operation on a Modbus Network. It also provides the basic setup procedures to operate the C-

More Boiler Controller and BMS II in each available Modbus Mode.

6.2 C-MORE BOILER CONTROLLER SETUP FOR MODBUS

OPERATION

The C-More Boiler Controller can be set up for three types of Modbus operating modes. These

modes are as follows:

Monitoring and Configuration Only

Modbus Direct Drive Control and Monitoring

Modbus Remote Setpoint Control and Monitoring

The following paragraphs provide the procedures necessary to set up the C-More Boiler

Controllers for each of the above modes of operation. These procedures assume that the

required wiring connections for Modbus operation have already been accomplished as described

in Section 4.

NOTE

The appropriate password must be entered in the Setup Menu of

the C-More Boiler Controller, prior to changing any of the current

settings. For detailed information on menu items, refer to the

appropriate Operation and Maintenance Manual for the Benchmark

Series or KC1000 Series units being used.

6.2.1 Monitoring and Configuration Control

In order for the C-More Boiler Controller to be recognized by the Modbus Master, a valid Network

Comm Address must be entered in the Setup Menu as follows: