Chapter 6

MODBUS

Communication

GF-114

C-More/BMS II/ACS Software Setup

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

83 of 200

The appropriate password must be entered in the Setup Menu of

the BMS II/ACS prior to changing any of the current settings. For

detailed information on menu items or change procedures, refer to

the BMS II/ACS operating instructions provided in GF-124.

6.3 BMS II/ACS SETUP FOR OPERATION AS A SLAVE TO AN EMS

MASTER

The BMS II/ACS can be programmed as a Slave to an EMS Master on the Modbus Network in

two ways:

Monitoring and Configuration Only

Modbus Remote Setpoint Control and Monitoring

The setup procedures for the above operating configurations are provided in paragraphs 6.3.1

and 6.3.2 which follow.

6.3.1 BMS II/ACS Monitoring and Configuration By An EMS Master

To set up the BMS II/ACS to be monitored or configured on the Modbus Network, entries must

be made in the RS232 Menu as follows:

1. Using the

MENU key on the BMS II/ACS front panel, select the RS232 MENU.

2. Scroll through the RS232 Menu and select the RS232 MODE option. The second line of

the display will show the currently selected RS232 Mode (MODBUS SLAVE or

NORMAL).

3. If MODBUS SLAVE is not displayed, press the

CHANGE key and toggle the display to

MODBUS SLAVE.

4. Press the

ENTER key to store the MODBUS SLAVE setting in memory.

5. While still in the RS232 MENU, scroll to the RS232 BAUDRATE option. Using the

CHANGE key and or ▼ arrow keys, select the appropriate baud rate being used on

the Modbus Network. Press the

ENTER key to store the selected baud rate.

6. Next, scroll to the MODBUS ADDRESS option. Using the

CHANGE key, and the ▲ or▼

arrow keys, select the desired address for the BMS II/ACS on the Modbus Network.

7. When the address is selected, press the

ENTER key to store the address in memory.

The BMS II/ACS is now set up to be monitored or configured on the Modbus Network.

6.3.2 BMS II/ACS Modbus Remote Setpoint Control By An EMS Master

To configure the BMS II/ACS for Remote Setpoint Control from an EMS Master, options must be

set in the RS232 Menu and Field Adjust Menu as follows:

1. Using the

MENU key on the BMS II/ACS front panel, select the RS232 MENU.

2. Scroll through the RS232 Menu and select the RS232 MODE option. The second line of

the display will show the currently selected RS232 Mode (MODBUS SLAVE or

NORMAL).

3. If MODBUS SLAVE is not displayed, press the

CHANGE key and toggle the display to

MODBUS SLAVE.

4. Press the

ENTER key to store the MODBUS SLAVE setting in memory.

5. While still in the RS232 MENU, scroll to the RS232 BAUDRATE option. Using the