Table 11 C-More Controller Status and Fault Messages -Cont.

Code

MESSAGE

DESCRIPTION

17

IGN SWTCH OPEN

DURING IGNITION

The Ignition Position Limit switch on the Air/Fuel valve opened
during ignition.

18

AIRFLOW FAULT

DURING IGN

The Blower Proof Switch opened during ignition.

19

AIRFLOW FAULT

DURING RUN

The Blower Proof Switch opened during run.

20

SSOV FAULT

DURING IGN

The SSOV switch closed or failed to open during ignition.

21

SSOV FAULT

DURING RUN

The SSOV switch closed for more than 15 seconds
during run.

22

FLAME LOSS

DURING IGN

The Flame signal was not seen during ignition or lost within 5
seconds after ignition.

23

FLAME LOSS

DURING RUN

The Flame signal was lost during run.

24

HIGH EXHAUST

TEMPERATURE

The High Exhaust Temperature Limit Switch is closed.

25

LOSS OF POWER

A power loss occurred. The time and date when power was
restored is displayed.

26

LOSS OF SENSOR

Not Currently Used

27

LOSS OF SIGNAL

Not Currently Used

28

HIGH O2 LEVEL

Not Currently Used

29

LOW O2 LEVEL

Not Currently Used

30

HIGH CO LEVEL

Not Currently Used

31

SSOV RELAY

FAILURE

A failure has been detected in one of the relays that control the
SSOV.

32

RESIDUAL

FLAME

The Flame signal was seen for more than 60 seconds during
standby.

33

HEAT DEMAND

FAILURE

The Heat Demand Relays on the Ignition board failed to
activate when commanded.

34

IGN SWTCH CLOSED

DURING PURGE

The Ignition Position Limit switch on the Air/Fuel valve closed
during purge.

35

PRG SWTCH CLOSED

DURING IGNITION

The Purge Position Limit switch on the Air/Fuel valve closed
during ignition.

36

SSOV

SWITCH OPEN

The SSOV switch opened during standby.