GF-122 AERCO XPC GATEWAY

189

Table 12 Boiler Control Module (BCM) Error Codes

CODE

DESCRIPTION

EFFECT

CORRECTION

RESET

17

Boiler Pipe is frozen.
FlowSensor temperature is
36°F or less.

Ignition is inhibited. Pump
runs for 5 min at max
speed.

Carefully defrost boiler

AUTOMATIC - when
FlowSensor is greater than
41°F.

18

Maximum Δ-temperature
protection. Flow
temperature - Return
Temperature > Water

Δ-

Temp Protection + 50°F

All burners turned OFF and
Pump ON at maximum
speed.

Check the system installation.

AUTOMATIC -

when Δ-

temperature < Water Δ-
Temp Protection.

19

High outlet temperature.
FlowSensor temperature >
203°F.

All burners turned OFF and
Pump ON at maximum
speed.

Check Flow Sensor or system pump

AUTOMATIC - when
FlowSensor < 176°F.

38

Settings Corrupted

Ignition is inhibited. Pump
runs for 5 min at max
speed.

Re-program the settings. Contact Factory

MANUAL - push reset
switch or cycle power.

50

Internal Failure

Ignition is inhibited.

Contact Factory for new BCM.

MANUAL - cycle the power.

58

FlowSensor fault.

All burners turned OFF.

Check flow sensor or wiring.

AUTOMATIC

97

Standby. No remote control
detected and Request input
is open.

Ignition is inhibited.

Close Request input for Manual operation.

MANUAL - push reset
switch or cycle power.

98

No BMM detected.

Ignition is not possible.

Check the BMM eBus wiring.

MANUAL - push reset
switch or cycle power.