GF-5030

Gas Supply Design Guide

TABLE 4

Pipe Sizing Table for 5 Pounds Pressure Capacity of Pipes of Different Diameters and Lengths in Cubic

Feet per Hour for an Initial Pressure of 5.0 psi with a 10% Pressure Drop and a Gas of 0.6 Specific Gravity

Pipe Size of

Schedule 40

Standard Pipe

(Inches)

Internal

Diameter

(Inches)

Total Equivalent Length of Pipe (Feet)

50

100

150

200

250

300

400

500

2.00

2.067

11786

8101

6505

5567

4934

4471

3827

3391

2.50

2.469

18785

12911

10368

8874

7865

7126

6099

5405

3.00

3.068

33209

22824

18329

15687

13903

12597

10782

9556

3.50

3.548

48623

33418

26836

22968

20365

18444

15786

13991

4.00

4.026

67736

46555

37385

31997

28358

25694

21991

19490

5.00

5.047

122544

84224

67635

57887

51304

46485

39785

35261

6.00

6.065

198427

136378

109516

93732

83073

75270

64421

57095

Venting of Gas Supply Regulators

AERCO’s general guidelines for venting of gas regulators are listed below. AERCO recommends that
these guidelines be followed to ensure the most reliable and proper operation of AERCO gas fired
equipment. It is also recommended that you consult local codes and the gas regulator manufacturer for
additional details. Always follow the most stringent guidelines available, including those listed below.

· When venting a gas supply regulator, the vent pipe must be no smaller than the regulator vent size.
· In a multiple unit installation, each regulator must have a separate vent line.
· Vent lines must not be manifolded together or with any other equipment at the site that also requires

atmospheric vents.

· When sizing the vent, pipe diameters must be increased by one pipe diameter every 20 equivalent

feet of pipe.
·

Each 90° elbow is equivalent to approximately:

Þ

2.5 feet for nominal pipe sizes of up to 3/4”

Þ

4.5 feet for nominal pipe sizes of up to 1-1/2”

Þ

10.5 feet for nominal pipe sizes of up to 4”

·

·

Each 45° elbow is equivalent to approximately:

Þ

1 foot for nominal pipe sizes of up to 3/4”

Þ

2 feet for nominal pipe sizes of up to 1-1/2”

Þ

5 feet for nominal pipe sizes of up to 4”




Pg. 7 of 10