Chapter 7

Innovation Series Water Heaters

GF-128

Troubleshooting Guide

USER MANUAL

OMM-0079_0B

PR1 - 07/21/11

AERCO International, Inc.

· 100 Oritani Dr. · Blauvelt, NY 10913 · Ph: 800-526-0288

Page 79 of 200

TABLE 7-1. WATER HEATER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

HIGH GAS

PRESSURE

1. Incorrect supply gas pressure.

2. Defective SSOV Actuator.

3. Defective High Gas Pressure Switch



1. Check to ensure gas pressure at inlet of SSOV is 2 psig

maximum.

2. If gas supply pressure downstream of SSOV Actuator cannot be

lowered, to 1.5” W.C. using the gas pressure adjustment screw
(see para. 4.3, step 10), the SSOV Actuator may be defective.

3. Remove the leads from the high gas pressure switch and

measure continuity across the common and normally closed
terminals with the unit not firing. Replace the switch if it does
not show continuity.

HIGH WATER TEMP

SWITCH OPEN

1. Faulty Water temperature switch.

2. Incorrect PID settings.


3. Faulty shell temperature sensor.


4. Unit in Manual mode

5. Unit setpoint is greater than Over

Temperature Switch setpoint.

6. System flow rate changes are

occurring faster than units can
respond.

1. Test the temperature switch to insure it trips at its actual water

temperature setting.

2. Check PID settings against Menu Default settings in the

Appendix. If the settings have been changed, record the current
readings then reset them to the default values.

3. Using the resistance charts in the Appendix C, Measure the

resistance of Shell sensor and BTU sensor at a known water
temperature.

4. If unit is in Manual Mode switch to Auto Mode.

5. Check setpoint of unit and setpoint of Temperature Switch;

Ensure that the temperature switch is set higher than the unit’s
setpoint.

6. If the system is a variable flow system, monitor system flow

changes to ensure that the rate of flow change is not faster than
what the units can respond to.

HIGH WATER

TEMPERATURE

1. See HIGH WATER TEMPERATURE

SWITCH OPEN.

2. Temp HI Limit setting is too low.

1. See HIGH WATER TEMPERATURE SWITCH OPEN.

2. Check Temp HI Limit setting.

IGN BOARD

COMM FAULT

1. Communication fault has occurred

between the PMC board and
Ignition/Stepper (IGST) board

1. Press CLEAR button and restart unit. If fault persists, contact

qualified Service Personnel.