Tighten connections to the torque values shown in Table 3, using an

insulated torque wrench and an insulated open-end wrench in counter-

torque, as shown in Figure 1.4.7.
Refer to Table 3 to verify that your hardware is correct for the battery type

being installed. Align cells so the inter-cell connectors match up with the holes

of the terminal posts.

SQUARE POST (5)

(two hole with

copper insert)

SQUARE POST (4)

(single hole with

copper insert)

FLAG TERMINAL (1)

SQUARE POST (2)

(no insert)

CHAIR TERMINAL (3)

SQUARE NO INSERT

(6)

FIGURE 1.4.6 Post and

Terminal Design

MULTICELL POST (7)

(with copper insert)

SQUARE POST (8)

(double cross

drilled solid copper)

FIGURE 1.4.7 - Torquing connections

Note:
Use the same torque values for connection to terminal plates or cable lugs added to battery posts.
Recommend 100% recheck of torques after assembly, using maintenance torque values.

RECTANGULAR

POST (9)

BLADE POST (10)

PART 1

RECEIVING AND INSTALLATION (CONTINUED)

Table 3 - Torque Requirements for Specific Cell/Unit Types

Bolt

Assembly

Standard

Optional Terminal

Design

Initial

Torque

inch

pounds

Mainte-

nance

Torque inch

pounds

Current Cell/

Unit Types

Discontinued Cell/

Unit Types

C

A

FLAG

(1)

70

60

DU & DCU MULTI-

CELL UNITS

DT & DCT MULTI-CELL

UNITS

C

B

SQUARE

NO

INSERT (2)

110

100

DU & DCU SINGLE

CELL UNITS

KT, KCT, LT, LCT

KAR, KCR 5-13

LAR, LCR 13-17

LCUN 19-33

LCY 544 & 660

4LCY 9-11

MULTI-CELL

DT & DCT SINGLE CELLS

KU & KCU SINGLE CELLS

KA & KC 7 to 13 PLATE

SINGLE CELLS

KCW & KCW 11 to 17 PLATE

SINGLE CELLS

KU & KC MULTI-CELLS

KT & KCT MULTI-CELLS
KCY & KCX MULTI-CELL

LCZ 9 TO 11 MULTI-CELLS

LCZ 13 to 17

LU & LCU 13 to 27 CELLS

LA & LC 13 to 17 CELLS

LY & LCY 13 to 17 CELLS

C

B

CHAIR

(3)

110

100

LCY290, 420

MULTI-CELL

ALL JC

MULTI-CELL

ALL JCW MULTI-CELL

KA & KC MULTI-CELL

KT & KCT MULTI-CELL

KCW MULTI-CELL

MHCSD, CJCSD & CJSD

C

N/A

CHAIR

(3)

160

125

LY & LCY 5 & 7 PLATE

XTL, XTLP, XTLA

XTH & XTHP

7&9 MULTI-CELL
XTJ MULTI-CELL

MULTI-CELL:

KAR, KCR, KT & KCT

KCW, KCY, KY & KCX

XTJ & XTK, LWC 9 & 11

LCZ 5 & 7

C

N/A

SQUARE

WITH

INSERT

(4 & 5)

160

125

XTL, XTLP & XTLA

11 & LARGER SIZES

KAR & KCR 15-21

LCY 35-39, LAR & LCR

19-33

SINGLE CELLS

LCU-19, LCU-27

LAR &LCR 13 & 15

TWO CELL

KY & KCY 17 to 25 CELLS

KA/KC 15 to 21 CELLS

KCX & KCW 19 to 33 CELLS

LCW, LCXL LY, LCY & LCZ 9

& 11 MULTI-CELL, LCV &

XTR/XTRP 17-21
XTR/XTRP 27-31

LCZ 19-39, LU & LCU 29

to 33,

LA & LC 19 to 33 CELLS

C

B

SQUARE

NO

INSERT (6)

110

100

MCT II

MT II

MCT-HP

MT/MCT & MR/MCR

D

N/A

MULTI-CELL

POST

(7)

160

125

XTL, XTLP & XTLA

11, 13 & 15

4LCY 9-11

LCY 544 & 660

INTER-CELL

N/A

C

N/A

SQUARE

(8)

160

125

LCT II 1700

N/A

C

N/A

RECTAN-

GULAR

(9)

110

100

DJ/DJU/XDJ

N/A

C

N/A

BLADE (10)

160

125

XTH, XTHP

N/A

RS1476/0215/CD

11

www.cdtechno.com