2.2 Storing charged and dry batteries

Storage of dry-charged batteries should be in a ventilated, weatherproof, cool and dry building. Remove any

packing container that indicates shipping damage and inspect the thermoplastic jar for cracks or damage. To

prevent foreign material or moisture from entering the cells,

do not remove the plastic film vent seal until cells

are to be filled with electrolyte, charged and prepared for installation.

CAUTION

Upon installation and filling, special attention must be directed to PART 3, Section 1, instructions for

activating and charging dry-charged batteries. Also refer to C&D Form RS-758.

SECTION 3 - PRE-INSTALLATION PLANNING
The cell arrangement, rack(s) and connections are typically installed using generic information provided by C&D.

However, a customized and detailed installation drawing may be obtained from C&D when placing your original

order at an additional charge.
The installer should plan the battery arrangement starting with the positive terminal of the battery to the negative

terminal. Planning should be completed before receipt of the battery. First, sketch a footprint of the rack location.

Check the applicable codes for clearance requirements. Allow sufficient aisle width to permit loading cells directly

to their ultimate location on the rack and clearance for maintenance including overhead clearance. Determine the

battery terminations and locations on the rack layout. The floor loading capacity of the room should be checked,

as well as its capability to hold anchor bolts.

Cells at the end of each row in stepped or tiered racks must be arranged for the shortest cable run between

steps and tiers. See the following illustration. Failure to do so will result in some cables being too short due to

terminal (post) locations especially on multi-cell units.

PART 1

RECEIVING AND INSTALLATION (CONTINUED)

Specific Gravity of Cell

Individual Cell Voltage

1.170

1.215

1.225

1.250

1.275

1.300

2.025

2.063

2.075

2.098

2.123

2.145

+

+

Inter-tier

connection

cables


+

Top tier, x number of cells

Mid tier, x number of cells

Bottom tier, x number of cells

Inter-tier

connection

cables

+


+

Top tier/step, x number of cells

Bottom tier/step, x number of cells

Top row

Bottom row

Inter-step

cable connection

STEP RACK

Inter-tier

cable connection

TIER RACK

Top row

Bottom row

RS1476/0215/CD

5

www.cdtechno.com

*Fully Charged with Electrolyte

Between High & Low Level Lines

Cell on Open Circuit for 24-72 Hours

If there are an even number of tiers or steps, the battery will terminate on a common end. If there are an odd

number of tiers or steps, the battery will terminate at opposite ends. Polarities below are shown for reference only.

WARNING

The positive and negative terminal

connections of a battery should never

be terminated within a multi-cell unit.

The positive and negative terminal

connections of a battery must be

from different cell containers properly

spaced to provide isolation between

the highest potential differences of

the battery.

TOP ROW

BOTTOM ROW

Unacceptable termination

*Table 2 - Open Circuit Cell Voltages