CAUTION

ELECTRICAL HAzARD — AUTHORIzED PERSONNEL

Before connecting battery to charger, it is important to note that several hazards are associated with

battery systems, particularly those used for large UPS applications where terminal voltages can approach

several hundred volts and currents may exceed several thousand amperes. By exercising proper care and

allowing only properly trained personnel to work on them, batteries should serve you well and perform

without incident. Observe precautions and become familiar with local, state, federal, and professional

codes and procedures. It is advisable to determine if the UPS topology includes an isolation input

transformer. If it does not, an electrical ground reference will be present at the battery.

CAUTION

If proper polarity is not observed when charging the battery, the battery or groups of reverse-connected

cells will be irreparably damaged.

4.10 Connecting battery to charger
Use only direct current (dc) for charging. With the charging source de-energized, connect the positive terminal of

the battery to the positive terminal of the charger or system bus, and the negative terminal of the battery to the

negative terminal of the charger or system bus. Check polarities with a voltmeter to be sure that connections are

correct. Energize the system by following the manufacturer’s procedures.

PART 1

RECEIVING AND INSTALLATION (CONTINUED)

Note: Always complete a record of open circuit voltage, initial charge, float charge readings and connection

resistances with DLRO. Retain the readings in your files for future reference. Any future warranty discussions

will require this information. For convenience, use Form RS-105. A sample is included in this manual. Make

a photocopy of the sample so the original will be available for subsequent use. The service life of your

battery will depend on boost charges (if in storage), its operating temperature, frequency of use and depth of

discharge, discharge rate, and float charge voltage and regulation.

Address the report to:

C&D TECHNOLOGIES, INC.

Attn.: Technical Service Department

1400 Union Meeting Road

Blue Bell, PA 19422

[email protected]

Terminal plates facilitate the connection of multiple power leads. They

are made of heavy copper, tin or lead-plated and formed to permit

connection to posts of various configurations. See Appendix A for

details of the terminal plates supplied in the standard accessory kits.

RS1476/0215/CD

13

www.cdtechno.com

NOTE: C&D recommends the use of lead-plated cable lugs on vented flooded lead acid batteries if

connections will be made directly to the posts of cells

Figure 1.4.9

Caution

Unsupported cables may cause excessive stress to

terminal plates and posts. The maximum unsupported

length of an inter-tier, inter-row or inter-rack cable should

be 3 feet. Cabling dropping from overhead cable supports

may have a maximum unsupported length of 4 feet.