Table 1 battery specifications – C&D Technologies RS-1826 Liberty Series 1000 FA Battery User Manual

Page 11

Advertising
background image

Model

FAM 12-100

FA 12-125*

FAM 12-150

Nominal

12 volts

12 volts

12 volts

voltage

Number

6 / Unit

6 / Unit

6 / Unit

of cells

Rated 8-hr

capacity

(ampere-

hours to

1.75 Vpc)

Internal

0.00042

0.000589

0.00043

resistance

Ohms

Ohms

Ohms

Short

circuit

current

Unit

9.05 in.

10.12 in.

12.63 in.

height

(230 mm)

(257 mm)

(323 mm)

Unit

length

(includes

handles)

Unit width

4.94 in.

6.93 in.

4.94 in.

(125 mm)

(176 mm)

(125 mm)

Weight

80 lbs. (41 kg)

120 lbs. (55 kg)

131 lbs. (60 kg)

Plate

thickness

positive

(3.55 mm)

negative

0.085 in.

0.088 in.

0.085 in.

(2.16 mm)

(2.23 mm)

(2.16 mm)

Threaded copper-

Threaded copper-

Threaded copper-

brass insert.

brass insert.

brass insert.

Fasten with

Fasten with

Fasten with

1/4-20 stainless

1/4-20 stainless

1/4-20 stainless

steel hex

steel hex

steel hex

bolt/washer.

bolt/washer.

bolt/washer.

9

TABLE 1 BATTERY SPECIFICATIONS

*FA 12-125 consists of (2) FA 6-125 units in an epoxy-painted steel jacket.

100 Ah to
10.5 volts

125 Ah to
10.5 volts

150 Ah to
10.5 volts

4000 A

2600 A

4610 A

21.95 in.

(558 mm)

16.60 in.

(415 mm)

21.95 in.

(558 mm)

0.140 in.

(3.81 mm)

0.150 in.

(3.55 mm)

0.140 in.

Terminal

Advertising