C&D Technologies RS-1826 Liberty Series 1000 FA Battery User Manual

Page 20

Advertising
background image

• Increases internal discharge or local action losses
• Lowers cell voltage for a given charge current
• Raises charging current for a given charge voltage
• Increases the rate of dry-out of electrolyte

Lower than normal temperatures have the opposite effect and
reduce capacity. In general, at proper float voltage, a battery in a
cool location will last longer than one in a warm location.

Note:

No temperature correction is required when operating at
77°F +/- 10°F, (25°C +/- 5.5°C). The following correction
factors apply for range not exceeding +/- 30°F from
nominal. For further assistance with temperature correction
factors, contact C&D TECHNOLOGIES.

If the operating temperature is other than 77°F (25°C), it is recom-
mended that the float voltage be changed as follows:

For temperatures other than 77°F (25°C), correct float voltage by
2 mV per degree F (3.6 mV per degree C):

• Add 2 mV (0.002 Volts) per degree F (3.6 mV per degree C)

below 77°F (25°C)

• Subtract 2 mV (0.002 Volts) per degree F (3.6 mV per degree C)

above 77°F (25°C)

Note:

Temperature compensation will materially improve battery
service life when provided.

2.3.5 Record keeping

As a minimum annual measurements of module voltage should be
taken and recorded. On occasion, if a long discharge has been
experienced, completely recharge the battery and take a set of
voltage readings recording them for future reference if the readings
are satisfactory. Provide remedial action or an equalize charge if
necessary.

Do not discharge a battery below the design final

voltage. Remedial action may be required if the battery was
discharged below its final design voltage. Very deep discharges can,
without an immediate recharge, completely deplete the electrolyte and
cause hydration. Failure to maintain records may void the warranty.

2.3.6 Connection maintenance

Check the torque of bolted connections annually. Refer to table 1 for
initial torque values. The same value may be used for re-torque.
Examine the connections for cleanliness and indicate any required
action on your records.