C&D Technologies RS-1826 Liberty Series 1000 FA Battery User Manual

Page 12

Advertising
background image

FV/Time

Models

1 hr.

3 hr.

5 hr.

8 hr.

10 hr.

20 hr.

FAM 12-100

66.3

28.1

18.5

12.4

10.2

5.5

1.75

FA 12-125

86.3

37.1

24

15.8

12.9

6.8

FAM 12-150

99.9

43

28.1

18.8

15.4

8.2

FAM 12-100

64.7

27.6

18.2

12.3

10.1

5.4

1.80

FA 12-125

83.2

35.8

23.2

15.4

12.6

6.6

FAM 12-150

96.2

42.4

27.8

18.6

15.3

8.1

FAM 12-100

1 hr

3 hr

5 hr

8 hr

10 hr

20 hr

1.84

FA 12-125

78.7

34

22.2

14.7

12.1

6.4

FAM 12-150

92.4

41.7

27.5

18.4

15.1

8

FAM 12-100

57.6

25.3

16.7

11.3

9.3

5

1.88

FA 12-125

72.8

31.6

20.7

13.8

11.3

6

FAM 12-150

92

41.2

27.3

18.3

15

8

FAM 12-100

55.1

24.3

16.1

10.9

9

4.8

1.90

FA 12-125

69.1

30.1

19.7

13.2

10.8

5.8

FAM 12-150

85.3

40.4

27

18.2

14.9

7.9

Ratings in Amperes at 77°F (25°C)

10

C&D Front Access products meet or exceed IEEE-485 at time of shipment.
Additional rates are available at www.cdstandbypower.net

Advertising