2.1.4 Initial charge records

At the completion of the initial charge and after the cells have been on
float charge for approximately one week, record voltages of the
individual cells or units, the total battery voltage and ambient
temperature. Retain this information in your files for future reference.
This information establishes one baseline for future reference. Refer to
RS-1511 found in the appendix. Make a photocopy of the form and
use it whenever necessary to record readings taken on the battery.

IMPORTANT

: Initial charge records and on-going maintenance

records are essential for review by C&D TECHNOLOGIES sales/
service agents in the event of a problem. Since records can materially
affect your warranty, be sure to maintain clear, signed, and dated
copies.

2.1.5 Warning labels

C&D TECHNOLOGIES, INC. provided a warning label to assist in
maintaining standby batteries and to advise you of certain hazards.

This label may be found on the battery cover

visible to anyone in

the immediate vicinity of the battery. Make certain that all individuals
who could be operating near the battery read the warning that is
intended to inform the individuals of basic safety practices.

SECTION 2 - BATTERY OPERATION

2.2.1 Float charge

The normal charging voltage to maintain the battery is called “Float
Charge” and is provided at a potential slightly higher than the full
charged open circuit voltage. The over potential is required to main-
tain properly polarized plates within the VRLA battery. Float voltages
may vary from 2.24 - 2.26 volts per cell at 77°F (25°C) depending
upon the frequency and depth of discharges.

Assuming full float service a (6) six cell 12 volt module should
be floated at 13.67 volts +/- .06 volts at 77°F (25°C).

2.2.2 Equalizing charge

Under normal operating conditions, it should not be necessary to
equalize batteries when charged at the recommended voltage in Table
2. An equalizing charge delivered at a voltage higher than the nominal
float voltage is used to restore uniform cell voltage to a battery.

Note 1:

Some hydrogen gas may be liberated at equalize charging
voltage.

FLUSH EYES
IMMEDIATELY

WITH
WATER.
GET

MEDICAL

HELP FAST

U.S. PAT. 4683647, 4752545, 5593796

OTHER PATENT PENDING

Leola, PA

(800) 543-8631

DANGER

HIGH VOLTAGE…

RISK OF SHOCK. DO NOT
TOUCH UNINSULATED
TERMINALS OR
CONNECTORS

SHIELD

EYES

EXPLOSIVE

GASES

CAN CAUSE

BLINDNESS OR INJURY

NO

• SPARKS
• FLAMES
• SMOKING

SULFURIC

ACID

CAN

CAUSE BLINDNESS
OR SEVERE BURNS

“DO NOT REMOVE VENT VALVES.”

VENTILATE WELL WHEN IN AN ENCLOSED

SPACE AND WHEN CHARGING.

SEE INSTALLATION, MAINTENANCE AND OPERATION

INSTRUCTIONS FOR IMPORTANT SAFETY PRECAUTIONS.

REPAIR SHOULD BE PERFORMED ONLY BY

A QUALIFIED SERVICE TECHNICIAN.

TORQUE SPECIFICATIONS

MODULE TO MODULE

25 - 30 ft-lb

TERMINAL PLATES

160 in-lb

TERMINAL TO NON-

5 ft-lb (INITIAL)

CONDUCTING MATERIAL

15 ft-lb (RE-TORQUE)

CONNECTORS

160 in-lb

®